Table 23: The minimum distances between cables in long parallel lines
The distance between
cables [m]
The length of the
shielded cable [m]
The distance between
cables [ft]
The length of the
shielded cable [ft]
0.3 ≤ 50 1.0 ≤ 164.0
1.0 ≤ 200 3.3 ≤ 656.1
6.4 CABLE INSTALLATION
6.4.1 ENCLOSURE SIZES MR8 AND MR9
1 MR9 only: Open the cover of the AC drive.
2 MR9 only: Loosen the screws and remove the
sealing plate.
A
A. The screws
VACON · 60 POWER CABLING
6
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/