10.1.3 MAINS VOLTAGE 525-690 V
Table 46: The power ratings of VACON
®
100 FLOW in mains voltage 525-690 V, 50-60 Hz, 3~
Enclosure
size
Drive type Loadability Motor shaft power
Continuous
current
I
Lout
[A]
Input
current I
Lin
[A]
10%
overload
current [A]
Max
current I
S
2s
600 V
mains
690 V
mains
10%
overload
40°C [hp]
10%
overload
40°C [kW]
MR8 0080 80.0 90.0 88.0 124.0 75.0 75.0
0100 100.0 106.0 110.0 160.0 100.0 90.0
0125 125.0 127.0 137.5 200.0 125.0 110.0
MR9 0144 144.0 156.0 158.4 250.0 150.0 132.0
0170 170.0 179.0 187.0 288.0 - 160.0
0208 208.0 212.0 228.8 340.0 200.0 200.0
MR10 0261 261.0 272.0 287.1 416.0 250.0 250.0
0325 325.0 330.0 357.5 522.0 300.0 315.0
0385 385.0 386.0 423.5 650.0 400.0 355.0
0416* 416.0 415.0 457.6 770.0 450.0 400.0
MR12 0460 460.0 477.0 506.0 832.0 450.0 450.0
0520 520.0 532.0 572.0 920.0 500.0 500.0
0590 590.0 597.0 649.0 1040.0 600.0 560.0
0650 650.0 653.0 715.0 1180.0 650.0 630.0
0750* 750.0 747.0 825.0 1300.0 700.0 710.0
0820* 820.0 813.0 902.0 1300.0 800.0 800.0
10.1.4 OVERLOAD CAPABILITY
The low overload means that if 110% of the continuous current (I
L
) is required for 1 minute
every 10 minutes, the remaining 9 minutes must be approximately 98% of I
L
or less. This is to
make sure that the output current is not more than I
L
during the duty cycle.
TECHNICAL DATA, VACON® 100 FLOW VACON · 117
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/