9 TECHNICAL DATA, VACON
®
100 INDUSTRIAL
9.1 AC DRIVE POWER RATINGS
9.1.1 MAINS VOLTAGE 208-240 V
Table 34: The power ratings of VACON
®
100 INDUSTRIAL in mains voltage 208-240 V, 50-60 Hz,
3~
Enclos
ure
size
Drive
type
Loadability Motor shaft power
Low High Max
curre
nt I
s
2s
230 V mains 230 V mains
Contin
uous
curre
nt
I
Lout
[A]
Input
curre
nt I
Lin
[A]
10%
over-
load
curre
nt [A]
Contin
uous
curre
nt
I
Hout
[A]
Input
curre
nt I
Hin
[A]
50%
over-
load
curre
nt [A]
10%
over-
load
40°C
[kW]
50%
over-
load
40°C
[kW]
10%
over-
load
40°C
[hp]
50%
over-
load
40°C
[hp]
MR8 0140 140.0 135.1 154.0 114.0 109.0 171.0 210.0 37.0 30.0 50.0 40.0
0170 170.0 162.0 187.0 140.0 133.0 210.0 280.0 45.0 37.0 60.0 50.0
0205 205.0 200.0 225.5 170.0 163.0 255.0 340.0 55.0 45.0 75.0 60.0
MR9 0261 261.0 253.0 287.1 211.0 210.0 316.5 410.0 75.0 55.0 100.0 75.0
0310 310.0 301.0 341.0 251.0 246.0 376.5 502.0 90.0 75.0 125.0 100.0
TECHNICAL DATA, VACON® 100 INDUSTRIAL VACON · 103
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
9

Table of Contents

Other manuals for Vacon 100 flow

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon 100 flow and is the answer not in the manual?

Vacon 100 flow Specifications

General IconGeneral
Protection classIP20
Communication interfaceRS-485
Operating temperature-10°C to +50°C
Storage temperature-40°C to +70°C
Ambient temperature-10°C to +40°C
Control methodSensorless vector control
Communication protocolsCANopen
ApprovalsCE, UL
I/O2 analog inputs
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature
Frequency range0 Hz to 400 Hz
Humidity5% to 95%, non-condensing
Voltage range208-240 V