10 TECHNICAL DATA, VACON
®
100 FLOW
10.1 AC DRIVE POWER RATINGS
10.1.1 MAINS VOLTAGE 208-240 V
Table 44: The power ratings of VACON
®
100 FLOW in mains voltage 208-240 V, 50-60 Hz, 3~
Enclosure
size
Drive type Loadability Motor shaft power
Continuous
current
I
Lout
[A]
Input
current I
Lin
[A]
10%
overload
current [A]
Max
current I
S
2s
230 V
mains
230 V
mains
10%
overload
40°C [kW]
10%
overload
40°C [hp]
MR8 0140 143.0 135.1 154.0 210.0 37.0 50.0
0170 170.0 162.0 187.0 280.0 45.0 60.0
0205 208.0 200.0 225.5 340.0 55.0 75.0
MR9 0261 261.0 253.0 287.1 410.0 75.0 100.0
0310 310.0 301.0 341.0 502.0 90.0 125.0
TECHNICAL DATA, VACON® 100 FLOW VACON · 115
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
10

Table of Contents

Other manuals for Vacon 100 flow

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon 100 flow and is the answer not in the manual?

Vacon 100 flow Specifications

General IconGeneral
Protection classIP20
Communication interfaceRS-485
Operating temperature-10°C to +50°C
Storage temperature-40°C to +70°C
Ambient temperature-10°C to +40°C
Control methodSensorless vector control
Communication protocolsCANopen
ApprovalsCE, UL
I/O2 analog inputs
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature
Frequency range0 Hz to 400 Hz
Humidity5% to 95%, non-condensing
Voltage range208-240 V

Related product manuals