12 Specifications
This chapter lists the UPS specifications.
12.1 Conformance and Standards
The UPS has been designed to comply with the European and international standards listed in Table 12.1 below.
Item No rm a tive refe ren ce
General safety requirements for UPS EN62040-1/IEC62040-1/BS62040-1
EMC requirements for UPS EN62040-2/IEC62040-2/BS62040-2 (Class C3)
Method of specifying the performance and test requirements of UPS EN62040-3/IEC62040-3/BS62040-3 (VFI SS 111)
Environmental aspects - requirements and reporting EN62040-4/IEC62040-4/AS62040-4 (VFI SS 111)
Table 12.1 European and international stan dards
N O T E: The p roduct stan dard s in this table incorp orate relevant com pliance clauses with generic IE C
and EN standards for safety (IEC /EN /B S60950 ), electrom agnetic em ission and im m unity
(IE C /EN /BS 6100 0 series) and construction (IEC /EN /BS60146 series and 60529).
12.2 Environmental Characteristics
Item N orm ative re fere nce
Rated p ower (k V A )
25 0
Noise within 1m (in the front) dB (A) 68
Altitude m ≤ 1500; derate power by 1% per 100 m between 1500 m and 3000 m
Relative humidity %RH 0 to 95%, non condensing
Operating temperature °C
0 to 50 °C; 0 to 40 °C (full load), 40 to 45 °C (90% load), 45 to 50 °C (80%
load)
Storage and transportation temperature for UPS °C Storage: -25 °C to +55 °C; transportation: -40 °C to +70 °C
Over-voltage level Level 2
Pollution level Level 2
Grid system TN, TT, IT
Table 12.2 E nvironm ental characteristics