Energy Saving Mode Activation
N O T E: Refer to the U PS m anual before activating Energy Saving M ode. An Operator can only enable
or disable Energy Saving M ode. The m odes available vary acco rd ing to the UP S type and system
configuration. The types available m ust be set up by som eo ne with either A d m inistrator or Service
access.
Energy Saving Mode may be activated or deactivated through the OPERATE menu screen. Two modes are available: Eco
Mode and Intelligent Parallel Mode.
Eco Mode permits the UPS to reduce power consumption by powering the load through bypass power when utility-supplied
power is within acceptable ranges. The inverter will remain in a state that will permit it to resume supplying power if the utility
power goes outside acceptable ranges.
Intelligent paralleling puts units in a sleep mode until required.
To activate or deactivate Energy Saving Mode:
1. Touch the Setup radio button for Energy Saving Mode Activation.
2. Enable or disable Energy Saving Mode.
3. Touch the Save button. The Save button is inactive until the activation state is changed.
5 Operator Control and Display Panel
69
Vertiv™ Liebert® APM Plus User Manual