Maintenance E 3000
8.14 Storing the Genset
Short term
If the genset sits idle for more than one month, exercise the genset at least two
hours each month by running the genset at approximately 1/2 rate power. A single
two-hour exercise period is preferred over several shorter periods.
Long term
If the genset is to be idle for more than 120 days:
1. Change the engine oil.
2. Place a tag on the genset designating engine oil viscosity.
3. Disconnect the battery.
4. Plug the exhaust tail pipe to keep out dirt, moisture, bugs, etc.
5. Clean the genset.
When returning the genset back into service:
1. Reconnect the battery.
2. Check the oil tag and change the engine oil if the oil viscosity is not appropriate
for the expected temperature.
3. Remove the plug from the exhaust tail pipe.
4. Inspect the genset.
5. Clean the genset if necessary.