Alarm List
Alarm Number (1000 to 1999)
Alarm List-361
1658 REDUCTION STOP
SPECIFIC. ERR(SV)
1 The servo float function was
used for the axis for which the
deceleration stop function was
enabled.
The servo float function
cannot be used for the axis
which the deceleration stop
function was enabled.
Setting error Check the JOB.
other If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
2 The specified axis speed
control function was executed
for the axis which the
deceleration stop function was
enabled.
Specified axis speed control
function cannot be used for
the axis which the
deceleration stop function was
enabled.
Setting error Check the JOB.
other If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
1659 MOTOR GUN
CHANGE PG PWR
ON ERR(SV)
Setting error Check if the PICK instruction was executed again for the axis where
executed the PICK instruction in the gun change system.
other If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
1660 MOTOR GUN
CHANGE SV ON
ERR(SV)
Setting error Check if the PICK instruction was executed again for the axis where
executed the PICK instruction in the gun change system.
Alarm
Number
Alarm Name Sub
Code
Meaning Cause Remedy