5 Replacing Parts
5.1 Replacing DX200 Parts
5-23
5.1.5 Checking and Replacing Fuses
5.1.5.1 Power ON Unit
The types of fuses on power supply ON unit
(
JZRCR-YPU5- ∆ ) are as follows.
Fig. 5-16: Power ON Unit (JZRCR-YPU5
-
∆
)
If the fuse is blown, replace it with the same type of fuse (supplied or
spare parts).
Parts No. Fuse Name Specification
1FU, 2FU AC Control power supply
fuse
0215010MXP
10A, 250V, Time lag fuse (LITTEL)
3FU,4FU AC cooling fan fuse GP25, 2.5A, 250V
(Daito Communication Apparatus
Co., Ltd.)
If the fuse seems to be blown, be sure to investigate its
cause, or blown again after the replacement.
(1FU),(2FU)
Fuse for the AC control
power supply
0215010MXP (10A, 250V)
(3FU),(4FU)
Fuse for the cooling fan
GP25 (2.5A 250V)