Alarm List
Alarm Number (4000 to 4999)
Alarm List-470
other If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
10 Failed to store the area. Software operation error
occurred
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
11 Measurement item setting
error
Communication error (1)Reset the alarm.
(2)If the alarm occurs again, check the setting of communication or
transmission side data is correctly set.
other If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
12 Tag setting error Communication error (1)Reset the alarm.
(2)If the alarm occurs again, check the setting of communication or
transmission side data is correctly set.
other If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
48 Wait status table FULL Communication error (1)Reset the alarm.
(2)If the alarm occurs again, check the setting of communication or
transmission side data is correctly set.
other If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
4126 CANNOT EXECUTE
AUTO PMT
1 System error Software operation error
occurred
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
2 PBOX cannot be edited. Setting error (1)Reset the alarm.
(2)Check the following setting.
I/O status of the edit prohibit signal
The edit prohibit signal cannot input.
Alarm
Number
Alarm Name
Sub
Code
Meaning Cause Remedy