Alarm List
Alarm Number (4000 to 4999)
Alarm List-487
4139 WRONG EXECUTION
OF PRINT INST
Setting error (1)Reset the alarm.
(2)Check the following settings.
∙ The setting of the PRINT output conversion spec (character string
specification)
If there is no problem in the setting, delete the corresponding PRINT
instruction and register again.
other If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
4140 WRONG EXECUTION
OF DIALOG INST
1 DIALOG instruction control
error
Setting error (1)Reset the alarm.
(2)Check the following settings.
∙ The tag setting of DIALOG instruction
If no fault is found, delete corresponding DIALOG instruction, and then
register again.
other If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
2 Messages and buttons are not
registered.
Setting error (1)Reset the alarm.
(2)Check the following settings.
∙ The information of DIALOG instruction message and button
other If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
3 Buttons are not registered. Setting error (1)Reset the alarm.
(2)Check the following settings.
∙ The information of DIALOG instruction button
other If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
4141 SNTP ERROR 1 The error on setting of time
difference value occurred in
the SNTP process of the
Ethernet function.
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
Alarm
Number
Alarm Name
Sub
Code
Meaning Cause Remedy