Drive Model Terminal
Recomm. Gauge
mm
2
(AWG, kcmil)
Wire Range
mm
2
(AWG, kcmil)
Screw
Size
Tightening Torque
N·m (lb.in.)
5A0017
R/L1, S/L2, T/L3
6.0
(10)
6.0 to 16
(10 to 6)
M5
3.6 to 4.0
(31.8 to 35.4)
U/T1, V/T2, W/T3
6.0
(10)
6.0 to 16
(10 to 6)
, 1, 2
6.0 to 16
(10 to 6)
B1, B2
6.0 to 10
(10 to 8)
2.7 to 3.0
(23.9 to 26.6)
10
(8)
6.0 to 10
(12 to 8)
M6
5.4 to 6.0
(47.8 to 53.1)
5A0022
R/L1, S/L2, T/L3
10
(8)
6.0 to 16
(10 to 6)
M5
3.6 to 4.0
(31.8 to 35.4)
U/T1, V/T2, W/T3
6.0
(10)
6.0 to 16
(10 to 6)
, 1, 2
6.0 to 16
(10 to 6)
B1, B2
6.0 to 10
(10 to 8)
2.7 to 3.0
(23.9 to 26.6)
10
(8)
6.0 to 10
(10 to 6)
M6
5.4 to 6.0
(47.8 to 53.1)
5A0027
5A0032
R/L1, S/L2, T/L3
16
(6)
16 to 25
(6 to 4)
M6
5.4 to 6.0
(47.8 to 53.1)
U/T1, V/T2, W/T3
16
(6)
16 to 25
(6 to 4)
, 1, 2
16 to 25
(6 to 4)
B1, B2
6.0 to 10
(10 to 8)
M5
2.7 to 3.0
(23.9 to 26.6)
16
(6)
10 to 16
(10 to 6)
M6
5.4 to 6.0
(47.8 to 53.1)
5A0041
R/L1, S/L2, T/L3
16
(6)
6.0 to 25
(10 to 3)
M8
9.0 to 11
(79.7 to 97.4)
U/T1, V/T2, W/T3
16
(6)
6.0 to 25
(10 to 3)
, 1
(6 to 1)
B1, B2
4.0 to 25
(12 to 3)
16
(6)
10 to 16
(6)
5A0052
R/L1, S/L2, T/L3
25
(4)
6.0 to 25
(10 to 3)
M8
9.0 to 11
(79.7 to 97.4)
U/T1, V/T2, W/T3
16
(6)
6.0 to 25
(10 to 3)
, 1
16 to 35
(6 to 1)
B1, B2
10 to 25
(8 to 3)
16
(6)
10 to 16
(6)
5A0062
R/L1, S/L2, T/L3
25
(4)
6.0 to 95
(10 to 4/0)
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
25
(4)
6.0 to 95
(10 to 4/0)
, 1
25 to 95
(4 to 4/0)
3
16 to 95
(6 to 4/0)
25
(4)
25
(4)
3.7 Main Circuit Wiring