H2 Multi-Function Digital Output Settings
H2-oo
Setting
Function LCD Display Description Page
AA Utility Start Delay Utility Delay
Closed: The drive is stopped and waiting for the utility delay timer set in P4-17 to
expire.
–
AB Main Feedback Lost Main FdBk Lost Closed: Main feedback is lost. –
AC Backup Feedback Lost Backup FdBk Lost Closed: Backup feedback is lost. –
100 to
1AC
Function 0 to AC with
inverse output
–
Inverts the output switching of the multi-function output functions.
Set the last two digits of 1oo to reverse the output signal of that specific function.
–
<1> Available in drive software versions PRG: 8551 and earlier.
<2> Available in drive software versions PRG: 8552 and later. Not available in drive models 4A0930 and 4A1200.
u
H3: Multi-Function Analog Inputs
No.
(Addr.
Hex)
Name LCD Display Description Values Page
H3-01
(0410)
Terminal A1 Signal
Level Selection
Term A1 Level
0: 0-10V,
(LowLim=0)
1: 0-10V, (BipolRef)
2: 4-20 mA
3: 0-20 mA
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
3: 0 to 20 mA
Note: Use Jumper S1 to set input terminal A1 for a
current or voltage input signal.
Default: 0
Range: 0 to 3
225
H3-02
(0434)
Terminal A1 Function
Selection
Term A1 FuncSel
Sets the function of terminal A1. Default: 0
Range: 0 to 32
225
H3-03
(0411)
Terminal A1 Gain
Setting
Terminal A1 Gain
Sets the level of the input value selected in H3-02 when 10 V is
input at terminal A1.
Default: 100.0%
Min.: -999.9
Max.: 999.9
225
H3-04
(0412)
Terminal A1 Bias
Setting
Terminal A1 Bias
Sets the level of the input value selected in H3-02 when 0 V is
input at terminal A1.
Default: 0.0%
Min.: -999.9
Max.: 999.9
225
H3-05
(0413)
Terminal A3 Signal
Level Selection
Term A3 Level
0: 0-10V,
(LowLim=0)
1: 0-10V, (BipolRef)
2: 4-20 mA
3: 0-20 mA
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
3: 0 to 20 mA
Note: Use Jumper S1 to set input terminal A3 for a
current or voltage input signal.
Default: 0
Range: 0 to 3
226
H3-06
(0414)
Terminal A3 Function
Selection
Term A3 FuncSel
Sets the function of terminal A3. Default: 20
Range: 0 to 32
226
H3-07
(0415)
Terminal A3 Gain
Setting
Terminal A3 Gain
Sets the level of the input value selected in H3-06 when 10 V is
input at terminal A3.
Default: 100.0%
Min.: -999.9
Max.: 999.9
227
H3-08
(0416)
Terminal A3 Bias
Setting
Terminal A3 Bias
Sets the level of the input value selected in H3-06 when 0 V is
input at terminal A3.
Default: 0.0%
Min.: -999.9
Max.: 999.9
227
H3-09
(0417)
Terminal A2 Signal
Level Selection
Term A2 Level
0: 0-10V,
(LowLim=0)
1: 0-10V, (BipolRef)
2: 4-20 mA
3: 0-20 mA
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
3: 0 to 20 mA
Note: Use Jumper S1 to set input terminal A2 for a
current or voltage input signal.
Default: 2
Range: 0 to 3
227
H3-10
(0418)
Terminal A2 Function
Selection
Term A2 FuncSel
Sets the function of terminal A2. Default: B
Range: 0 to 32
227
H3-11
(0419)
Terminal A2 Gain
Setting
Terminal A2 Gain
Sets the level of the input value selected in H3-10 when 10 V
(20 mA) is input at terminal A2.
Default: 100.0%
Min.: -999.9
Max.: 999.9
227
H3-12
(041A)
Terminal A2 Bias
Setting
Terminal A2 Bias
Sets the level of the input value selected in H3-10 when 0 V (0
or 4 mA) is input at terminal A2.
Default: 0.0%
Min.: -999.9
Max.: 999.9
227
B.8 H Parameters: Multi-Function Terminals
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
383