4.5 Pump Application Presets
The following sections list the parameters affected by the different Application Presets.
Note: Setting A1-03 to 6011 or 6012 changes the Quick Start and Preset parameters (tables below) and also changes HAND Mode so that it is no
longer lower-limited by the minimum pump frequency or the thrust frequency. Also, the default for P1-06 when in RPM mode is 1800 RPM
instead of 2400 RPM.
u
Modified Parameters Depending on A1-03 Setting
The following tables show the parameters that are set depending on the A1-03 initialization:
A1-03 = 6009
(A1-06 = 9)
Pump Down Level
A1-03 = 6010
(A1-06 = 10)
Geothermal Mode
A1-03 = 6011
(A1-06 = 11)
VTC Pressure Control
A1-03 = 6012
(A1-06 = 12)
Pivot Panel VTC
Parameter Value Parameter Value Parameter Value Parameter Value
A1-02 0 b1-01 5 A1-02 0 A1-02 0
b5-09 1 b5-01 0 b1-03 1 b1-02 1
b5-39 2 H3-10 21 b5-03 5 b1-03 0
P1-02 6 o1-08 180 C1-01 15.0 s b5-03 5.0 s
P2-01 2 C1-02 15.0 s C1-01 20.0 s
P2-23 0.00% E1-04 65.0 Hz C1-02 20.0 s
P9-18 0.00% E2-04 4 E1-04 65.0 Hz
L2-01 0 E2-04 4
L5-01 0 L2-01 0
P1-03 100.0 PSI L5-01 0
P1-06 35.0 Hz L5-04 300.0 s
P2-03 15 s P1-03 210.0 PSI
<1>
P2-23 0.00% P1-06 35.0 Hz
P3-50 35.0 Hz P1-11
<2>
210.0 PSI
P3-60 35.0 Hz P1-40 60.0 Hz
P3-70 35.0 Hz P2-03 15 s
P4-12 0.0 Hz P2-23 0.00%
P5-02 6.0 Hz P4-12 0.0 Hz
Q5-03 40.0 PSI P5-01 0
Q5-06 50.0 PSI P5-02 6.0 Hz
Q5-09 20.0 PSI
Q5-10 5.0 min
Q5-11 2
Q5-16 1
Q5-17 3.0 s
H2-01 80H
H2-02 81H
H2-03 82H
P1-40 60.0 Hz
P3-01 2
P3-04 5.0 PSI
P3-06 5.0 Hz
P3-07 7.0 s
P3-10 2.0 PSI
<1> Default is 100.0 PSI in drive software versions PRG: 8553 and earlier.
<2> Available in drive software versions PRG: 8554 and later.
4.5 Pump Application Presets
146
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual