H1 Multi-Function Digital Input Selections
H1-oo
Setting
Function LCD Display Description Page
AD
Select Secondary PI
Parameters
Select PI2 Parms
Closed: Uses the secondary PI controller Proportional and Integral adjustments
(S3-06 and S3-07) instead of the primary PI controller Proportional and Integral
adjustments (b5-02 and b5-03). Only valid when S3-01 = 0 (secondary PI
controller disabled).
Note: This multi-function input has no effect on the secondary PI
controller. It is only used for the primary PI controller (b5-oo).
AF
Emergency Override
Forward Run
EmergOverrideFWD
Closed: Run the drive forward using the speed set in S6-02.
B0
Emergency Override
Reverse Run
EmergOverrideREV
Closed: Run the drive in reverse using the speed set in S6-02.
<1> Available in drive software versions PRG: 8552 and later. Not available in drive models 4A0930 and 4A1200.
u
H2: Multi-Function Digital Outputs
No.
(Addr.
Hex)
Name LCD Display Description Values Page
H2-01
(040B)
Terminal M1-M2
function selection
(relay)
M1-M2 Func Sel
Refer to H2 Multi-Function Digital Output Settings on pages
224 to 224 for descriptions of setting values.
Default: 37
Range: 0 to 1AC
223
H2-02
(040C)
Terminal M3-M4
function selection
(relay)
M3/M4 Func Sel
Default: 42
<1>
Range: 0 to 1AC
223
H2-03
(040D)
Terminal MD-ME-MF
Function Selection
MD/ME/MF Func Sel
Default: E
Range: 0 to 1AC
223
H2-06
(0437)
Watt Hour Output Unit
Selection
Pwr Mon Unit Sel
Outputs a 200 ms pulse signal when the watt-hour counter
increases by the units selected.
0: 0.1 kWh units
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units
Default: 0
Range: 0 to 4
H2-31
(09D1)
<2>
Terminal M1/M2 On-
Delay Time M1/M2 On
M1/M2 On Delay
Sets the amount of time needed for the programmed function
(H2-01) to be active before M1/M2 closes.
Default: 0.0 s
Range: 0.0 to
3000.0
H2-32
(09D2)
<2>
Terminal M3/M4 On-
Delay Time
M3/M4 On Delay
Sets the amount of time needed for the programmed function
(H2-02) to be active before M3/M4 closes.
Default: 0.0 s
Range: 0.0 to
3000.0
H2-33
(09D3)
<2>
Terminal MD/ME/MF
On-Delay Time
MD/ME/MF OnDelay
Sets the amount of time needed for the programmed function
(H2-03) to be active before MD/MF closes, or ME/MF opens.
Default: 0.0 s
Range: 0.0 to
3000.0
H2-41
(09D9)
<2>
Terminal M1/M2 Off-
Delay Time
M1/M2 Off Delay
Sets the amount of time needed for the programmed function
(H2-01) to be inactive before M1/M2 opens.
Default: 0.0 s
Range: 0.0 to
3000.0
H2-42
(09DA)
<2>
Terminal M3/M4 Off-
Delay Time
M3/M4 Off Delay
Sets the amount of time needed for the programmed function
(H2-02) to be inactive before M3/M4 opens.
Default: 0.0 s
Range: 0.0 to
3000.0
H2-43
(09DB)
<2>
Terminal MD/ME/MF
Off-Delay Time
MD/ME/MF Off Dly
Sets the amount of time needed for the programmed function
(H2-03) to be inactive before MD/MF opens, or ME/MF closes.
Default: 0.0 s
Range: 0.0 to
3000.0
<1> Default is F in drive software versions PRG: 8551 and earlier.
<2> Available in drive software versions PRG: 8554 and later. Not available in drive models 4A0930 and 4A1200.
H2 Multi-Function Digital Output Settings
H2-oo
Setting
Function LCD Display Description Page
0 During run During RUN 1 Closed: A Run command is active or voltage is output.
1 Zero speed Zero Speed
Open: Output frequency is above the minimum output frequency set in E1-09.
Closed: Output frequency is below the minimum output frequency set in E1-09.
B.8 H Parameters: Multi-Function Terminals
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
379
B
Parameter List