No.
(Addr.
Hex)
Name LCD Display Description
Analog
Output Level
Unit
U1-92
(0BA7)
Pump Status Pump Status
Displays Pump Running Status.
U1
-
92=
00000000
Drive
Pump 2
Pump 3
Pump 4
Pump 5
Pump 6
Not used
Not used
1
1
1
1
1
1
0
0
No signal output
available
–
U1-93
(0BA8)
Total Setpoint
Compensation
Total SP Comp.
Displays the total absolute Setpoint Compensation. No signal output
available
dep. on
P1-02
U1-94
(0BA9)
Motor Speed Motor Speed
Displays the absolute value of the output frequency (U1-02)
converted to RPM.
No signal output
available
1 RPM
U1-96
(0BAB)
<6>
PI Auxiliary Control
Feedback Level
PI Aux FB Level
Displays the PI Auxiliary Control Feedback Level (H3-oo =
27).
N/A
Unit
dep. on
Q6-21
Res.
dep. on
Q6-22
U1-97
(0BAC)
Water Level Water Level
Displays the amount of water above the water level sensor. Full scale:
10 V = Q4-02
0.1 ft.
U1-98
(0BAD)
Suction Pressure Suction Pressure
Displays the amount of suction pressure. Full scale:
10 V = Q5-02
0.1 PSI
or ”Hg
U1-99
(0BAE)
<7>
Anti-No-Flow Timer ANF Timer
The Anti-No-Flow reduces the output frequency when this
value reaches the P2-24 setting.
No signal output
available
0.1 s
<1> Display is in the following units:
2A0004 to 2A0040, 4A0002 to 4A0023, and 5A0007 to 5A0017: 0.01 A units.
2A0056 to 2A0415, 4A0031 to 4A0675, and 5A0022 to 5A0242: 0.1 A units.
4A0930 and 4A1200: 1 A units.
<2> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.
<3> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
<4> The display resolution depends on the ND selection. This value has two decimal places (0.01 kW) if the drive is set for a maximum applicable
motor capacity up to and including 11 kW, and one decimal place (0.1 kW) if the maximum applicable motor capacity is higher than 11 kW.
<5> Available in drive software versions PRG: 8551 and later.
<6> Available in drive software versions PRG: 8552 and later. Not available in drive models 4A0930 and 4A1200.
<7> Monitor is available through the Quick Monitor screen.
u
U2: Fault Trace
No.
(Addr.
Hex)
Name LCD Display Description
Analog
Output Level
Unit
U2-01
(0080)
Current Fault Current Fault
Displays the current fault. No signal output
available
–
U2-02
(0081)
Previous Fault Last Fault
Displays the previous fault. No signal output
available
–
U2-03
(0082)
Frequency Reference at
Previous Fault
Frequency Ref
Displays the frequency reference at the previous fault. No signal output
available
0.01 Hz
U2-04
(0083)
Output Frequency at
Previous Fault
Output Freq
Displays the output frequency at the previous fault. No signal output
available
0.01 Hz
U2-05
(0084)
Output Current at
Previous Fault
Output Current
Displays the output current at the previous fault.
Note: The unit is expressed in 1 A for models 4A0930
and 4A1200.
No signal output
available
<1>
<2>
B.16 U: Monitors
440