YASKAWA iQpump1000 - U2: Fault Trace

YASKAWA iQpump1000
508 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
No.
(Addr.
Hex)
Name LCD Display Description
Analog
Output Level
Unit
U1-92
(0BA7)
Pump Status Pump Status
Displays Pump Running Status.
U1
-
92=
00000000
Drive
Pump 2
Pump 3
Pump 4
Pump 5
Pump 6
Not used
Not used
1
1
1
1
1
1
0
0
No signal output
available
U1-93
(0BA8)
Total Setpoint
Compensation
Total SP Comp.
Displays the total absolute Setpoint Compensation. No signal output
available
dep. on
P1-02
U1-94
(0BA9)
Motor Speed Motor Speed
Displays the absolute value of the output frequency (U1-02)
converted to RPM.
No signal output
available
1 RPM
U1-96
(0BAB)
<6>
PI Auxiliary Control
Feedback Level
PI Aux FB Level
Displays the PI Auxiliary Control Feedback Level (H3-oo =
27).
N/A
Unit
dep. on
Q6-21
Res.
dep. on
Q6-22
U1-97
(0BAC)
Water Level Water Level
Displays the amount of water above the water level sensor. Full scale:
10 V = Q4-02
0.1 ft.
U1-98
(0BAD)
Suction Pressure Suction Pressure
Displays the amount of suction pressure. Full scale:
10 V = Q5-02
0.1 PSI
or ”Hg
U1-99
(0BAE)
<7>
Anti-No-Flow Timer ANF Timer
The Anti-No-Flow reduces the output frequency when this
value reaches the P2-24 setting.
No signal output
available
0.1 s
<1> Display is in the following units:
2A0004 to 2A0040, 4A0002 to 4A0023, and 5A0007 to 5A0017: 0.01 A units.
2A0056 to 2A0415, 4A0031 to 4A0675, and 5A0022 to 5A0242: 0.1 A units.
4A0930 and 4A1200: 1 A units.
<2> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.
<3> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
<4> The display resolution depends on the ND selection. This value has two decimal places (0.01 kW) if the drive is set for a maximum applicable
motor capacity up to and including 11 kW, and one decimal place (0.1 kW) if the maximum applicable motor capacity is higher than 11 kW.
<5> Available in drive software versions PRG: 8551 and later.
<6> Available in drive software versions PRG: 8552 and later. Not available in drive models 4A0930 and 4A1200.
<7> Monitor is available through the Quick Monitor screen.
u
U2: Fault Trace
No.
(Addr.
Hex)
Name LCD Display Description
Analog
Output Level
Unit
U2-01
(0080)
Current Fault Current Fault
Displays the current fault. No signal output
available
U2-02
(0081)
Previous Fault Last Fault
Displays the previous fault. No signal output
available
U2-03
(0082)
Frequency Reference at
Previous Fault
Frequency Ref
Displays the frequency reference at the previous fault. No signal output
available
0.01 Hz
U2-04
(0083)
Output Frequency at
Previous Fault
Output Freq
Displays the output frequency at the previous fault. No signal output
available
0.01 Hz
U2-05
(0084)
Output Current at
Previous Fault
Output Current
Displays the output current at the previous fault.
Note: The unit is expressed in 1 A for models 4A0930
and 4A1200.
No signal output
available
<1>
<2>
B.16 U: Monitors
440
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual