B.2 A: Initialization Parameters
The A parameter group creates the operating environment for the drive. This includes the parameter Access Level, Motor
Control Method, Password, User Parameters and more.
u
A1: Initialization
No.
(Addr.
Hex)
Name LCD Display Description Values Page
A1-00
(0100)
<1>
Language Selection
Select Language
0: English
1: (Japanese)
2: Deutsch
3: Français
4: Italiano
5: Español
6: Português
0: English
1: Japanese
2: German
3: French
4: Italian
5: Spanish
6: Portuguese
Default: 0
Range: 0 to 6
A1-01
(0101)
<2>
Access Level Selection
Access Level
0: Operation Only
1: User Parameters
2: Advanced Level
3: Lock parameters
0: View and set A1-01 and A1-04. Uo-oo parameters can also
be viewed.
1: User Parameters (access to parameters selected by the user,
A2-01 to A2-32)
2: Advanced Access (access to view and set all parameters)
3: Lock parameters
Default: 2
Range: 0 to 3
210
A1-02
(0102)
Control Method Selection
Control Method
0: V/f Control
2: Open Loop Vector
0: V/f Control
2: Open Loop Vector Control
Default: 0
Range: 0, 2
A1-03
(0103)
Initialize Parameters
Init Parameters
0: No Initialize
1110: User Initialize
2220: 2-Wire Initial
3330: 3-Wire Initial
5550: Term->Cntrl Int
6008: Pressure Control
6009: Pump down level
6010: Geothermal
mode
6011: VTC Pressure Ctl
6012: Pivot Panel VTC
6013: Adv PressureCtrl
6014: Pivot Panel Sub
7770: General purpose
7771: Sub Mtr GP Oper
0: No initialization
1110: User Initialize (parameter values must be stored using
parameter o2-03)
2220: 2-Wire initialization
3330: 3-Wire initialization
5550: Terminal->Control Initialize
6008: Pressure Control
6009: Pump down level
6010: Geothermal mode
6011: VTC pressure control
6012: Pivot Panel VTC
<3>
6013: Advanced Pressure Control
<3>
6014: Pivot Panel Submersible
<4>
7770: General purpose
7771: Submersible Motor General Purpose
Note: A1-03 is initially set to "6008" from the factory,
although the keypad will always display “0”.
Default: 0
Range: 0 to 5550;
6008 to 6014;
7770, 7771
210
A1-04
(0104)
Password Enter Password
When the value set into A1-04 does not match the value set into
A1-05, parameters A1-01 through A1-03 and A2-01 through A2-33
cannot be changed.
Default: 0000
Min.: 0000
Max.: 9999
A1-05
(0105)
Password Setting Select Password
A1-06
(0127)
Application Preset
Application Sel
0: Pressure Control
1: General Purpose
2: Sub Mtr GP Oper
5: General Ext HOA
6: General HOA Keys
8: Pressure Control
9: Pump Down Level
10: Geothermal Mode
11: VTC Pressure Ctl
12: Pivot Panel VTC
13: Adv PressureCtrl
14: Pivot Panel Sub
Note: This parameter is not settable. It is used as a
monitor only.
0: Pressure Control
1: General Purpose
2: Sub Mtr GP Oper
5: General Ext HOA
<3>
6: General HOA Keys
<3>
8: Pressure Control
9: Pump Down Level
10: Geothermal Mode
11: VTC Pressure Ctl
12: Pivot Panel VTC
13: Adv PressureCtrl
14: Pivot Panel Sub
<4>
Default: 0
Range: 0 to 2; 5, 6;
8 to 14
A1-08
<3>
(0F00)
Custom Initialize Modes
Custom InitModes
0: No Initialize
3005: General Ext HOA
3006: General HOA
Keys
0: No Initialization
3005: General Ext HOA
3006: General HOA Keys
Default: 0
Range: 0, 3005,
3006
212
<1> Parameter setting value is not reset to the default value when the drive is initialized.
<2> Default setting value is dependent on the Initialization parameter A1-03.
<3> Available in drive software versions PRG: 8552 and later. Not available in drive models 4A0930 and 4A1200.
<4> Available in drive software versions PRG: 8553 and later. Not available in drive models 4A0930 and 4A1200.
B.2 A: Initialization Parameters
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
351
B
Parameter List

Table of Contents

Other manuals for YASKAWA iQpump1000

Related product manuals