U6: Operation Status Monitors
No.
(Addr.
Hex)
Name LCD Display Description
Analog
Output Level
Unit
U6-01
(0051)
Motor Secondary
Current (Iq)
Mot SEC Current
Displays the value of the motor secondary current (Iq). Motor
rated secondary current is 100%.
10 V: Motor
secondary rated
current
0.1%
U6-02
(0052)
Motor Excitation
Current (Id)
Mot EXC Current
OLVOLVOLVOLV
Displays the value calculated for the motor excitation current
(Id). Motor rated secondary current is 100%.
10 V: Motor
secondary rated
current
0.1%
U6-05
(0059)
Output Voltage
Reference (Vq)
Voltage Ref (Vq)
OLVOLVOLVOLV
Output voltage reference (Vq) for the q-Axis.
10 V: 200 Vrms
<1>
0.1 Vac
U6-06
(005A)
Output Voltage
Reference (Vd)
Voltage Ref (Vd)
OLVOLVOLVOLV
Output voltage reference (Vd) for the d-Axis.
10 V: 200 Vrms
<1>
0.1 Vac
U6-07
(005F)
q-Axis ACR Output ACR(q) Output
OLVOLVOLVOLV
Displays the output value for current control relative to motor
secondary current (q-Axis).
10 V: 200 Vrms
<1>
0.1%
U6-08
(0060)
d-Axis ACR Output ACR(d) Output
OLVOLVOLVOLV
Displays the output value for current control relative to motor
secondary current (d-Axis).
110 V: 200
Vrms
<1>
0.1%
<1> Values shown are specific to 200 V class drives. Double the values for 400 V class drives. Multiply the values by 2.875 for 600 V class drives.
Note: Fault histories are not kept when CPF00, CPF01, CPF06, CPF24, oFA00, oFb00, oFC00, Uv1, Uv2, or Uv3 occur.
u
U7: CASE Monitors
No.
(Addr.
Hex)
Name LCD Display Description
Analog
Output Level
Unit
U7-01
(0051)
CASE Software
Number
CASE Software #
Displays the CASE software version number. No signal output
available
–
u
U9: Operation Status Monitors
No.
(Addr.
Hex)
Name LCD Display Description
Analog
Output Level
Unit
U9-01
(1901)
Network PI Feedback Net PI Feedback
Displays the network PI feedback recognized by the iQpump
MEMOBUS network.
No signal output
available
Dep. on
P1-02
U9-02
(1902)
<2>
Network Activity iQ Net Activity
Displays network traffic. A fluctuating number from 0 to 10000
denotes activity, while a relatively constant 0 denotes no
activity.
No signal output
available
<1>
U9-03
(1903)
<2>
Time to Alternate Time to Alternate
Displays the time remaining before a drive requests the
alternation mode set in P9-04.
No signal output
available
min
U9-04
(1904)
Running Queue
Number
Running Queue No
Displays the position in the iQPump MEMOBUS Multiplex
running queue.
No signal output
available
–
<1> Unit changes based on network status.
<->: Drive cannot communicate to other drives
<+>: Drive is a node on a network
<M>: Drive is the master on an iQpump network.
<2> Monitor is available through the Quick Monitor screen.
B.16 U: Monitors
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
447