B.3 b: Application
Application parameters configure the source of the Run command, DC Injection Braking, Speed Search, timer functions, PID
control, the Dwell function, Energy Savings, and other application-related settings.
u
b1: Operation Mode Selection
No.
(Addr.
Hex)
Name LCD DIsplay Description Values Page
b1-01
(0180)
Frequency Reference
Selection 1
Ref Source 1
0: Operator
1: Analog Input
2: Serial Com
3: Option PCB
4: Pulse Input
5: Geothermal
0: HOA keypad
1: Analog input terminals
2: MEMOBUS/Modbus communications
3: Option PCB
4: Pulse input (terminal RP)
5: Geothermal Mode (Frequency reference dependent on
temperature input (H3-0o = 21)
Default: 0
Range: 0 to 5
214
b1-02
(0181)
Run Command
Selection 1
Run Source 1
0: Operator
1: Digital Inputs
2: Communication
3: Option PCB
6: AUTOKey + Term
7: AUTOKey + Serial
8: AUTOKey + Option
0: HOA keypad
1: Digital input terminals
2: MEMOBUS/Modbus communications
3: Option PCB
6: AUTOKey + Term
<2>
7: AUTOKey + Serial
<2>
8: AUTOKey + Option
<2>
Default: 0
Range: 0 to 3; 6
to 8
217
b1-03
(0182)
Stopping Method
Selection
Stopping Method
0: Ramp to Stop
1: Coast to Stop
2: DCInj to Stop
3: Coast w/Timer
0: Ramp to stop
1: Coast to stop
2: DC Injection Braking to stop
3: Coast with timer
Default: 1
Range: 0 to 3
218
b1-04
(0183)
Reverse Operation
Selection
Reverse Oper
0: Reverse Enabled
1: Reverse Disabled
0: Reverse enabled
1: Reverse disabled
Default: 1
Range: 0, 1
b1-07
(0186)
Run Command
Retention when Source
is Changed
RunCmd@SrcChange
0: Require Cycle
1: Retain Run Cmd
Determines whether the run command is retained when the
Sequence Selection is changed
0: Require Cycle
1: Retain Run Command
Default: 0
Range: 0, 1
b1-08
(0187)
Run Command
Selection in
Programming Mode
RUN dur PRG Mode
0: Run
Disabled@PRG
1: Run Enabled@PRG
2: Prg only @ Stop
0: Run command is not accepted while in Programming Mode.
1: Run command is accepted while in Programming Mode.
2: Prohibit entering Programming Mode during run.
Default: 0
Range: 0 to 2
b1-11
(01DF)
Run Delay at Stop
(Back Spin Timer)
Run Delay @ Stop
Sets the amount of time that the drive will disallow the
reapplication of the Run command after the Run command is
lost. b1-11 is active for all b1-03 settings.
If set to zero and b1-03 = 3 (Coast to Stop w/ Timer), a
combination of C1-02 and output frequency determine the
length of time. Otherwise, no run delay will be applied.
Default: 0.0 s
Min.: 0.0
Max.: 6000.0
b1-12
(01E0)
<1>
Run Delay Memory
Selection
Run Dly Mem Sel
Determines whether the Run Delay Timer is saved to the
EEPROM during power loss.
0: Disabled
1: Only at Stop
2: Running & Stop
Note: A JVOP-183 HOA Keypad must be plugged into
the drive for settings 1 and 2 to function. If the
keypad is removed, b1-12 will function as setting
0 (Disabled).
Default: 2
Range: 0 to 2
b1-14
(01C3)
Phase Order Selection
Rotation Sel
0: Standard
1: SwitchPhaseOrder
0: Standard
1: Switch phase order (reverses the direction of the motor)
Default: 0
Range: 0, 1
b1-15
(01C4)
<1>
Frequency Reference
Selection 2
Ref Source 2
0: Operator
1: Analog Input
2: Serial Com
3: Option PCB
4: Pulse Input
Enabled when a multi-function digital input set for “External
Reference” (H1-oo = 2) closes.
0: Operator
1: Analog Input
2: Serial Communications
3: Option PCB
4: Pulse Input
Default: 0
Range: 0 to 4
B.3 b: Application
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
353