Name LCD Display Description Values Page
H5-12
(043D)
Run Command Method
Selection
Run CommandSel
0: FWD Run &REV
Run
1: Run & FWD/REV
0: FWD/Stop, REV/Stop
1: Run/Stop, FWD/REV Default: 0
Range: 0, 1
457
H5-13
(043E)
<3>
Power-up CALL Alarm
Powr-up CALL Alm
0: Disabled
1: Enabled
Determines whether a CALL alarm is triggered at power-up
when communication with the external controller has not been
established.
0: Disabled
1: Enabled
Default: 0
Range: 0, 1
–
H5-14
(0FB4)
<3>
Communication Error
(CE) Go-To- Frequency
CE Go-To-Freq
Sets the speed at which the drive will run when H5-04 is set to
4 (Run at H5-14) and a CE error is present.
Default: 0.0 Hz
Min.: 0.0
Max.: 400.0
457
H5-15
(0FB5)
<3>
Communication Error
(CE) Go-To-Timeout
CE Go-To-Timeout
Sets the amount of time that the drive will run at the speed set
in H5-14 before triggering a CE fault when H5-04 is set to 4
(Run at H5-14) and a CE error is present.
Setting this parameter to 0 will disable the time-out.
Default: 0 s
Min.: 0
Max.: 6000
457
H5-16
(0FB6)
<3>
Communication Error
Fault Restart Selection
CE Fault Restart
0: No Retry
1: Retry
Determines whether the CE fault can be restarted (L5-01).
0: No Retry
1: Retry
Default: 0
Range: 0, 1
457
<1> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands.
<2> When P1-01, Pump Mode, is set to 3 (MEMOBUS network), the range is dependent on P9-25, Highest Node Address.
<3> Available in drive software versions PRG: 8552 and later. Not available in drive models 4A0930 and 4A1200.
u
H6: Pulse Train Input
No.
(Addr.
Hex)
Name LCD Display Description Values Page
H6-01
(042C)
Pulse Train Input
Terminal RP Function
Selection
Term RP Func Sel
0: Frequency Ref
1: PID Feedback
2: PID Set Point
5: Flow Meter
0: Frequency reference
1: PID feedback value
2: PID setpoint value
5: Flow meter
Note: When this parameter is set to 5, parameters H6-02
to H6-04 and H6-08 are ignored.
Default: 0
Range: 0 to 2; 5
–
H6-02
(042D)
Pulse Train Input
Scaling
Term RP Scaling
Sets the terminal RP input signal frequency that is equal to 100%
of the value selected in H6-01.
Default: 1440 Hz
Min.: 100
Max.: 32000
–
H6-03
(042E)
Pulse Train Input Gain Terminal RP Gain
Sets the level of the value selected in H6-01 when a frequency
with the value set in H6-02 is input.
Default: 100.0%
Min.: 0.0
Max.: 1000.0
–
H6-04
(042F)
Pulse Train Input Bias Terminal RP Bias
Sets the level of the value selected in H6-01 when 0 Hz is input.
Default: 0.0%
Min.: -100.0
Max.: 100.0
–
H6-05
(0430)
Pulse Train Input Filter
Time
Term RP Flt Time
Sets the pulse train input filter time constant.
Default: 0.50 s
Min.: 0.00
Max.: 2.00
–
H6-08
(043F)
Pulse Train Input
Minimum Frequency
RP Lower Limit
Sets the minimum frequency for the pulse train input to be
detected. Enabled when H6-01 = 0, 1, or 2.
Default: 0.5 Hz
Min.: 0.1
Max.: 1000.0
–