<2> Available in drive software versions PRG: 8553 and later. Not available in drive models 4A0930 and 4A1200.
<3> Unit text is set by P1-18, Prime Loss Detection Method.
<4> Available in drive software versions PRG: 8551 and later.
<5> Maximum value is 300.0 in drive software versions PRG: 8553 and earlier.
<6> Available in drive software versions PRG: 8552 and later. Not available in drive models 4A0930 and 4A1200.
u
P5: Pump HAND Mode
No.
(Addr.
Hex)
Name LCD Display Description Values Page
P5-01
(0D2C)
HAND Mode Ref
Source
Hand Mode 1 Src
0: Analog Input
1: Hand Ref 1 (OPR)
Sets the HAND Mode reference.
0: Analog input
Note: Analog input is defaulted to input A3 (0-10 V).
1: P5-02 (HAND reference)
Default: 1
Range: 0, 1
P5-02
(0D2D)
HAND Reference 1 HAND Reference 1
Sets the frequency reference used when HAND Mode is active
and P5-01 is set to 1.
Default: 40.0 Hz
Min.: 0
Max.: [E1-04]
240
P5-03
(0D2E)
HAND/AUTO During
Run Selection
HAND/AUTO @Run
0: Disabled
1: Enabled
Selects whether the drive will permit switching between HAND
and AUTO Modes while running.
0: Disabled
1: Enabled
Default: 0
Range: 0, 1
P5-04
(0D2F)
HAND Key Function
Selection
Oper HAND Key
0: Disabled
1: Enabled
Enables and disables the HAND key on the HOA keypad.
0: Disabled
1: Enabled
Default: 1
Range: 0, 1
240
P5-05
(0D30)
HAND Reference 2 HAND Reference 2
Sets the frequency reference used when HAND Mode 2 is
active.
Default: 0.0 Hz
Min.: 0.0
Max.: [E1-04]
P5-06
(0D31)
HAND Ref. 1 Loss of
Prime Level
HandRef1 LOP Lvl
Detects loss of prime in the pump.
When the measured quantity determined by P1-18 drops below
this level for the time set in P1-20 and the output frequency is
at the level set in P5-02, a “Loss of Prime” condition occurs.
The drive responds to the “Loss of Prime” condition depending
on the setting of P1-22, Loss of Prime Selection.
Default: 0.0 A
<1>
Min.: 0.0
Max.: 1000.0
P5-07
(0D32)
HAND Ref. 2 Loss of
Prime Level
HandRef2 LOP Lvl
Detects loss of prime in the pump.
When the measured quantity determined by P1-18 drops below
this level for the time set in P1-20 and the output frequency is
at the level set in P5-05, a “Loss of Prime” condition occurs.
The drive responds to the “Loss of Prime” condition depending
on the setting of P1-22, Loss of Prime Selection.
Default: 0.0 A
<1>
Min.: 0.0
Max.: 1000.0
P5-09
(0D34)
HAND References Set
via Motor Operated Pot
Selection
Hand MOP Sel
0: Disabled
1: Enabled
Selects whether parameters P5-02 and P5-05 are changed via
MOP from the home screen.
0: Disabled
1: Enabled
Default: 0
Range: 0, 1
<1> Unit text is set by P1-18, Prime Loss Detection Method.
B.12 P: Pump Parameters