Setting 2: Run Command
Triggers the digital output when there is an active Run command.
n
P5-02: HAND Reference 1
Sets the frequency reference of HAND mode. When the drive is stopped, pressing the HAND key will start the drive and the
drive will accelerate to the P5-02 setting.
No. Parameter Name Setting Range Default
P5-02 HAND Reference 1 0.0 to E1-04 40.0 Hz
n
P5-04: HAND Key Function Selection
Selects whether the HAND key on the HOA keypad is active. Disabling this function by setting P5-04 to 0 will prevent the
drive from entering HAND Mode.
No. Parameter Name Setting Range Default
P5-04 HAND Key Function Selection 0, 1 1
Setting 0: Disabled
Setting 1: Enabled
n
P6-12: Accumulation Level - Thousands
Sets the accumulated volume that will trigger the Accum Level alarm, Accum Level fault, or the Accum Level Fault – Auto
Flow Accum Reset.
No. Name Setting Range Default
P6-12 Accumulation Level - Thousands 0 to 999 0 gal
n
P6-15: Accumulation Behavior
Selects the drive response when the accumulated volume reaches the level set in parameters P6-11 to P6-14.
No. Name Setting Range Default
P6-15 Accumulation Behavior 0 to 5 1
Setting 0: No display
Setting 1: Alarm only
Setting 2: Fault
Setting 3: Fault - Auto flow accum reset
Setting 4: Stop and alarm
Setting 5: Stop, alarm, and reset flow accumulation
n
P6-17: High Flow Level
Sets the level above which the flow must rise for longer than the time set in P6-18 to trigger a High Flow fault or alarm.
A setting of 0.0 disables High Flow detection.
No. Name Setting Range Default
P6-17 High Flow Level 0.0 to 6000.0 0.0 GPM
n
P6-19: High Flow Select
Determines drive response when a High Flow condition is detected.
No. Name Setting Range Default
P6-19 High Flow Select 0 to 3 1
4.7 Basic iQpump Setup and Application Preset Parameters
240
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual