Name LCD Display Description Values Page
E1-04
(0303)
Maximum Output
Frequency
Max Frequency
These parameters are only applicable when E1-03 is set to F.
To set linear V/f characteristics, set the same values for E1-07
and E1-09.
In this case, the setting for E1-08 will be disregarded. Ensure
that the four frequencies are set according to these rules:
E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
Output Voltage (V)
Frequency (Hz)
E1-05
E1-12
E1-13
E1-08
E1-10
E1-09 E1-07 E1-06 E1-11 E1-04
Default: 60.0 Hz
Min.: 40.0
Max.: 400.0
E1-05
(0304)
Maximum Voltage Max Voltage
Default: 230 V
<1>
Min.: 0.0
Max.: 255.0
<1>
E1-06
(0305)
Base Frequency Base Frequency
Default: 60.0 Hz
Min.: 0.0
Max.: E1-04
E1-07
(0306)
Middle Output
Frequency
Mid Frequency A
Default: 3.0 Hz
Min.: 0.0
Max.: E1-04
E1-08
(0307)
Middle Output
Frequency Voltage
Mid Voltage A
Default: 15.0 V
<1>
Min.: 0.0
Max.: 255.0
<1>
E1-09
(0308)
Minimum Output
Frequency
Min Frequency
Default: 1.5 Hz
(V/f)
0.5 Hz (OLV)
Min.: 0.0
Max.: E1-04
E1-10
(0309)
Minimum Output
Frequency Voltage
Min Voltage
Default: 10.2 V
(V/f)
2.0 V (OLV)
<1>
Min.: 0.0
Max.: 255.0
<1>
E1-11
(030A)
<4>
Middle Output
Frequency 2
Mid Frequency B
Default: 0.0 Hz
Min.: 0.0
Max.: E1-04
E1-12
(030B)
<4>
Middle Output
Frequency Voltage 2
Mid Voltage B
Default: 0.0 V
Min.: 0.0
Max.: 255.0
<1>
E1-13
(030C)
Base Voltage Base Voltage
Default: 0.0 V
<3>
Min.: 0.0
Max.: 255.0
<1>
<1> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
<2> Parameter setting value is not reset to the default value when the drive is initialized.
<3> When Auto-Tuning is performed, E1-13 and E1-05 will be set to the same value.
<4> Parameter ignored when E1-11 (Motor 1 Mid Output Frequency 2) and E1-12 (Motor 1 Mid Output Frequency Voltage 2) are set to 0.0.
u
E2: Motor 1 Parameters
No.
(Addr.
Hex)
Name LCD Display Description Values Page
E2-01
(030E)
Motor Rated Current Motor Rated FLA
Sets the motor nameplate full load current in amps.
Automatically set during Auto-Tuning.
Default:
<1>
Min.: 10% of
drive rated
current
Max.: 200% of
drive rated
current
<2>
222
E2-02
(030F)
Motor Rated Slip Motor Rated Slip
Sets the motor rated slip. Automatically set during Auto-Tuning.
Default:
<1>
Min.: 0.00 Hz
Max.: 20.00 Hz
E2-03
(0310)
Motor No-Load Current No-Load Current
Sets the no-load current for the motor. Automatically set during
Auto-Tuning.
Default:
<1>
Min.: 0 A
Max.: E2-01
<2>
B.6 E: Motor Parameters
366
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual