B.16 U: Monitors
Monitor parameters allow the user to view drive status, fault information, and other data concerning drive operation.
u
U1: Operation Status Monitors
No.
(Addr.
Hex)
Name LCD Display Description
Analog
Output Level
Unit
U1-01
(0040)
<7>
Frequency Reference Frequency Ref
Monitors the frequency reference. Display units are determined
by o1-03.
10 V: Max
frequency
0.01 Hz
U1-02
(0041)
<7>
Output Frequency Output Freq
Displays the output frequency. Display units are determined by
o1-03.
10 V: Max
frequency
0.01 Hz
U1-03
(0042)
<7>
Output Current Output Current
Displays the output current.
Note: The unit is expressed in 1 A for models 4A0930
and 4A1200.
10 V: Drive
rated current
<1>
<2>
U1-04
(0043)
Control Method Control Method
0: V/f Control
2: OLV Control
No signal output
available
–
U1-05
(0044)
Motor Speed Motor Speed
OLVOLVOLVOLV
Displays the motor speed feedback. Display units are
determined by o1-03.
10 V: Max
frequency
0.01 Hz
U1-06
(0045)
<7>
Output Voltage
Reference
Output Voltage
Displays the output voltage.
10 V: 200 Vrms
<3>
0.1 Vac
U1-07
(0046)
<7>
DC Bus Voltage DC Bus Voltage
Displays the DC bus voltage.
10 V: 400 V
<3>
1 Vdc
U1-08
(0047)
<7>
Output Power Output kWatts
Displays the output power (this value is calculated internally). 10 V: Drive
capacity
(motor capacity)
kW
<4>
U1-09
(0048)
Torque Reference Torque Reference
OLVOLVOLVOLV
Monitors the internal torque reference.
10 V: Motor
rated torque
0.1%
U1-10
(0049)
<7>
Input Terminal Status Input Term Sts
Displays the input terminal status.
U1
-
10=
00000000
Digital input 1
(terminal S1 enabled)
Digital input 2
(terminal S2 enabled)
Digital input 3
(terminal S3 enabled)
Digital input 4
(terminal S4 enabled)
Digital input 5
(terminal S5 enabled)
Digital input 6
(terminal S6 enabled)
Digital input 7
(terminal S7 enabled)
Digital input 8
(terminal S8 enabled)
1
1
1
1
1
1
1
1
No signal output
available
–
B.16 U: Monitors