EasyManua.ls Logo

YASKAWA iQpump1000 - U: MONITORS

YASKAWA iQpump1000
508 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
B.16 U: Monitors
Monitor parameters allow the user to view drive status, fault information, and other data concerning drive operation.
u
U1: Operation Status Monitors
No.
(Addr.
Hex)
Name LCD Display Description
Analog
Output Level
Unit
U1-01
(0040)
<7>
Frequency Reference Frequency Ref
Monitors the frequency reference. Display units are determined
by o1-03.
10 V: Max
frequency
0.01 Hz
U1-02
(0041)
<7>
Output Frequency Output Freq
Displays the output frequency. Display units are determined by
o1-03.
10 V: Max
frequency
0.01 Hz
U1-03
(0042)
<7>
Output Current Output Current
Displays the output current.
Note: The unit is expressed in 1 A for models 4A0930
and 4A1200.
10 V: Drive
rated current
<1>
<2>
U1-04
(0043)
Control Method Control Method
0: V/f Control
2: OLV Control
No signal output
available
U1-05
(0044)
Motor Speed Motor Speed
OLVOLVOLVOLV
Displays the motor speed feedback. Display units are
determined by o1-03.
10 V: Max
frequency
0.01 Hz
U1-06
(0045)
<7>
Output Voltage
Reference
Output Voltage
Displays the output voltage.
10 V: 200 Vrms
<3>
0.1 Vac
U1-07
(0046)
<7>
DC Bus Voltage DC Bus Voltage
Displays the DC bus voltage.
10 V: 400 V
<3>
1 Vdc
U1-08
(0047)
<7>
Output Power Output kWatts
Displays the output power (this value is calculated internally). 10 V: Drive
capacity
(motor capacity)
kW
<4>
U1-09
(0048)
Torque Reference Torque Reference
OLVOLVOLVOLV
Monitors the internal torque reference.
10 V: Motor
rated torque
0.1%
U1-10
(0049)
<7>
Input Terminal Status Input Term Sts
Displays the input terminal status.
U1
-
10=
00000000
Digital input 1
(terminal S1 enabled)
Digital input 2
(terminal S2 enabled)
Digital input 3
(terminal S3 enabled)
Digital input 4
(terminal S4 enabled)
Digital input 5
(terminal S5 enabled)
Digital input 6
(terminal S6 enabled)
Digital input 7
(terminal S7 enabled)
Digital input 8
(terminal S8 enabled)
1
1
1
1
1
1
1
1
No signal output
available
B.16 U: Monitors