Changing Parameter Settings or Values
This example explains changing C1-02 (Deceleration Time 1) from 10.0 seconds (default) to 20.0 seconds.
Note: During serial communication writing, if a parameter change is also attempted via the HOA keypad, a “BUSY - WRITE PROTECTED”
message will display. Parameter change will not be possible from the HOA keypad until an Enter command is received via the serial
communication to finish the serial writing process.
Step Display/Result
1. Turn on the power to the drive. The initial display appears.
- MODE -
U5-99= 0.0PSI
U1-02= 0.00Hz
U1-91= 0.0PSI
DRV
Auto Setpoint
Rdy
<-MONITOR->
LSEQ
LREF
2.
Press or until the Parameter Setting Mode screen appears.
Home
- MODE - PRG
Programming
FWD
3.
Press to enter the parameter menu tree.
-PRMSET-
Initialization
Select Language
PRG
FWD
A1-00= 0
Home
DATA
4.
Press or to select the C parameter group.
-PRMSET-
Basic Setup
Accel Time 1
PRG
FWD
C1-01= 20.0 sec
FWD
Home
DATA
5.
Press two times.
-PRMSET-
Accel/Decel
Accel Time 1
PRG
FWD
C1-01= 20.0sec
-PRMSET-
C1-01= 20.0sec
(0.0~6000.0)
“20.0 sec”
PRG
Accel Time 1
FWD
Home Home
DATA DATA
6.
Press or to select parameter C1-02.
-PRMSET-
C1-02= 10.0sec
(0.0~6000.0)
“10.0 sec”
PRG
Decel Time 1
FWD
Home
DATA
7.
Press to view the current setting value (10.0 s). The leftmost digit flashes.
-PRMSET-
C1-02= 0010.0sec
(0.0~6000.0)
“10.0 sec”
PRG
Decel Time 1
Home
FWD
8.
Press
F2
or until the desired number is selected. “1” flashes.
-PRMSET-
C1-02=0010.0sec
(0.0~6000.0)
“10.0 sec”
PRG
Decel Time 1
Home
FWD
9.
Press and enter 0020.0.
-PRMSET-
C1-02=0020.0sec
(0.0~6000.0)
“10.0 sec”
PRG
Decel Time 1
Home
FWD
10.
Press to confirm the change.
Entry Accepted
11. The display automatically returns to the screen shown in Step 6.
-PRMSET-
C1-02= 20.0sec
(0.0~6000.0)
“10.0 sec”
PRG
Decel Time 1
FWD
Home
DATA