Name LCD Display Description Values Page
P3-60
(11E5)
Pump 3 Frequency
Shutdown Level
P3 Shutdown Freq
Sets the level used for the multiplex pumping operation.
Parameter is active only when P3-02 is set to 0 or 2.
Parameter function is similar to P3-50, except for Pump 3
instead of Pump 2.
Default: 40.0 Hz
Min.: 0.0
Max.: 400.0
235
P3-70
(11EF)
Pump 4 Frequency
Shutdown Level
P4 Shutdown Freq
Sets the level used for the multiplex pumping operation.
Parameter is active only when P3-02 is set to 0 or 2.
Parameter function is similar to P3-50, except for Pump 4
instead of Pump 2.
Default: 40.0 Hz
Min.: 0.0
Max.: 400.0
235
P3-80
(11F9)
Pump 5 Frequency
Shutdown Level
P5 Shutdown Freq
Sets the level used for the multiplex pumping operation.
Parameter is active only when P3-02 is set to 0 or 2.
Parameter function is similar to P3-50, except for Pump 5
instead of Pump 2.
Default: 40.0 Hz
Min.: 0.0
Max.: 400.0
P3-90
(1203)
Pump 6 Frequency
Shutdown Level
P6 Shutdown Freq
Sets the level used for the multiplex pumping operation.
Parameter is active only when P3-02 is set to 0 or 2.
Parameter function is similar to P3-50, except for Pump 6
instead of Pump 2.
Default: 40.0 Hz
Min.: 0.0
Max.: 400.0
<1> Unit is determined by P1-02, System Units, setting.
<2> Available in drive software versions PRG: 8551 and later.
u
P4: Pump Advanced
No.
(Addr.
Hex)
Name LCD Display Description Values Page
P4-01
(0CFA)
Pre-Charge Level Pre-Charge Level
Runs the drive at the frequency set in P4-02.
The drive will stop when one of the following conditions occurs:
The feedback level rises above the level set in P4-01
The pre-charge time set in P4-03 expires
The low water digital input is deactivated (#8F)
Default: 0.0 PSI
<1>
Min.: 0.0
Max.: 6000.0
235
P4-02
(0CFB)
Pre-Charge Frequency Pre-Charge Freq.
Sets the frequency reference used when the Pre-Charge function
is active.
Default: 0.0 Hz
Min.: 0.0
Max.: [E1-04]
235
P4-03
(0CFC)
Pre-Charge Time Pre-Charge Time
Sets the maximum allowed Pre-Charge time.
When P1-01 is set to 3 (MEMOBUS network), the function is
active only on the first drive to run in the network.
Setting this parameter to 0.0 disables the function.
Default: 0.0 min
Min.: 0.0
Max.: 3600.0
235
P4-04
(0CFD)
<2>
Pre-Charge Message
Style
Pre-Charge Msg
0: Full Screen Msg
1: Home Mon Text
Selects how the “Pre-charge Active” message is displayed on
the operator.
0: Full Screen Message
1: Home Monitor Text
Default: 0
Range: 0, 1
238
P4-05
(0CFE)
Pre-Charge Loss of
Prime Level
Pre-Charge LOP
Detects loss of prime in the pump.
When the measured quantity determined by P1-18 drops below
this level for the time set in P1-20 and the output frequency is
at the level set in P4-02, a “Loss of Prime” condition occurs.
The drive responds to the “Loss of Prime” condition depending
on the setting of P1-22, Loss of Prime Selection.
Default: 0.0 A
<3>
Min.: 0.0
Max.: 1000.0
P4-06
(0CFF)
Pre-Charge Frequency 2 Pre-Charge Freq2
Sets the frequency reference used when the Pre-Charge function
2 is active.
Setting this parameter to 0.0 disables the function.
Default: 0.0 Hz
Min.: 0.0
Max.: [E1-04]
P4-07
(0D00)
Pre-Charge Time 2 Pre-Charge Time2
Sets the time at which the drive will spend at the Pre-Charge
frequency 2 speed during pre-charge.
Setting this parameter to 0.0 disables the function.
Default: 0.0 min
Min.: 0.0
Max.: 3600.0
P4-08
(0D01)
Pre-Charge Loss of
Prime Level 2
Pre-Charge LOP 2
Detects loss of prime in the pump.
When the measured quantity determined by P1-18 drops below
this level for the time set in P1-20 and the output frequency is
at the level set in P4-06, a “Loss of Prime” condition occurs.
The drive responds to the “Loss of Prime” condition depending
on the setting of P1-22, Loss of Prime Selection.
Default: 0.0 A
<3>
Min.: 0.0
Max.: 1000.0
P4-10
(0D03)
AUTO Mode Operator
Run Power Down
Storage
AUTO RunPwr Loss
0: Disabled
1: Enabled
Stores the run status in AUTO Mode when operating from the
HOA keypad (b1-02 = 0).
0: Disabled
1: Enabled
Default: 0
Range: 0, 1
238
B.12 P: Pump Parameters
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
409
B
Parameter List