5.8 Auto-Tuning
u
Types of Auto-Tuning
The drive offers different types of Auto-Tuning for induction motors. Refer to the tables below to select the type of Auto-
Tuning that bests suits the application.
n
Auto-Tuning for Induction Motors
This feature automatically sets the V/f pattern and motor parameters E1-oo and E2-oo for an induction motor.
Table 5.8 Types of Auto-Tuning for Induction Motors
Type Setting Application Conditions and Benefits
Control Mode
V/f OLV
Stationary Auto-Tuning for
Line-to-Line Resistance
T1-01 = 2
The drive is used in V/f Control and other Auto-Tuning selections are
not possible.
Perform when entering motor data manually while using motor cables
longer than 50 m.
Drive and motor capacities differ.
Tunes the drive after the cable between the drive and motor has been
replaced with a cable over 50 m long. Assumes Auto-Tuning has
already been performed.
Should not be used for any vector control modes unless the motor cable
has changed.
YES YES
Rotational Auto-Tuning for
V/f Control
T1-01 = 3
Recommended for applications using Speed Estimation Speed Search
or using the Energy Saving function in V/f Control.
Assumes motor can rotate while Auto-Tuning is executed. Increases
accuracy for certain functions like torque compensation, slip
compensation, Energy Saving, and Speed Search.
YES
Stationary
Auto-Tuning 2
T1-01 = 4
Motor and load cannot be decoupled and the load is higher than 30%.
A motor test report is available. After entering the no-load current and
the rated slip, the drive calculates and sets all other motor-related
parameters.
YES
Table 5.9 lists the data that must be entered for Auto-Tuning. Make sure this data is available before starting Auto-Tuning.
The necessary information is usually listed on the motor nameplate or in the motor test report provided by the motor
manufacturer.
Table 5.9 Auto-Tuning Input Data
Input Value Input Parameter Unit
Tuning Type (T1-01)
2
Line-to-Line
Resistance
3
Rotational for V/f
Control
4
Stationary 2
Control Mode A1-02 0, 2 0 2
Motor rated power T1-02 kW YES YES YES
Motor rated voltage T1-03 Vac YES YES
Motor rated current T1-04 A YES YES YES
Motor rated frequency T1-05 Hz YES YES
Number of motor poles T1-06 - YES YES
Motor rated speed T1-07 r/min YES YES
Motor no-load current T1-09 A YES
Motor rated slip T1-10 Hz YES
Motor iron loss T1-11 W YES
5.8 Auto-Tuning