EasyManua.ls Logo

YASKAWA iQpump1000 - Page 439

YASKAWA iQpump1000
508 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
No.
(Addr.
Hex)
Name LCD Display Description
Analog
Output Level
Unit
U1-29
(07AA)
Software No. (PWM) CPU 3 SW Number
PWM ID
Note: This monitor is only displayed in models 4A0930
and 4A1200.
No signal output
available
U1-75
(0851)
Time-Hour/Minute Time Hr Min HHMM
Displays the current time (Hours and Minutes). No signal output
available
U1-76
(0852)
Date – Year Date Year
Displays the current year. No signal output
available
U1-77
(0853)
Date – Month/Day Date Mo Day MMDD
Displays the current date (Month and Date). No signal output
available
U1-78
(0854)
Date – Week Day Date Week
Displays the current day of the week.
0: Sunday
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
No signal output
available
U1-79
(0B9A)
<5>
PI Feedback Back-up PI Fdbk Backup
Displays the PI Feedback Back-up signal (H3-oo = 24) used
when the primary PI Feedback (H3-oo = B) is lost.
No signal output
available
dep. on
P1-02
U1-80
(0B9B)
Geothermal
Temperature Input
Geothermal Temp
Displays the geothermal temperature input after the gain and
bias have been applied. This temperature is used by the
Geothermal Function to determine the proper frequency at
which to run the drive.
This monitor is internally limited to -999.9 °F to +999.9 °F.
No signal output
available
0.1 °F
U1-81
(0B9C)
<6>
Differential PI
Feedback
Diff PI Feedback
Differential Feedback signal (H3-oo = 28).
No signal output
available
dep. on
P1-02
U1-82
(0B9D)
<6>
Two Motor Time to
Alternate
2Motor Alt Time Time remaining before making a motor switch.
No signal output
available
min
U1-83
(0B9E)
Flow Rate Flow Rate
Displays the flow rate based on the pulse input frequency or the
analog voltage (flow rate input) and parameters P6-01 and
P6-04.
A 2-second first order filter will be applied to this monitor.
Full scale: P6-01
dep. on
P6-04
and
P6-22
U1-84
(0B9F)
Accumulation Level -
Millions
Volume * 1000000
Displays the recorded volume from the flow meter (pulse input
or analog voltage).
Total volume is calculated as follows:
Total Volume = (U1-84 * 1000000) + (U1-85 * 1000) + U1-86
+ U1-87
No signal output
available
dep. on
P6-16
U1-85
(0BA0)
Accumulation Level -
Thousands
Volume * 1000
U1-86
(0BA1)
Accumulation Level -
Ones
Volume * 1
U1-87
(0BA2)
Accumulation Level -
Decimal
Volume * 0.0001
U1-88
(N/A)
<6>
Total Volume
Accumulated
Total Vol (gal) or Total
Vol (A-F)
Displays the total volume. Full scale: N/A
dep. on
P6-16
U1-89
(N/A)
<6>
Delta Volume
Accumulated
Delta Vol (gal) or Total
Vol (A-F)
Displays the delta volume: Total Volume (U1-88/U1-84 to
U1-87) - Starting Delta Volume (P6-36 to P6-39).
Full scale: N/A
dep. on
P6-16
U1-90
(0BA5)
Pump Setpoint Pump Setpoint
Displays the PID Setpoint. No signal output
available
dep. on
P1-02
U1-91
(0BA6)
<7>
Pump Feedback Pump Feedback
Displays the PID Feedback.
No signal output
available
dep. on
P1-02
B.16 U: Monitors
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual
439
B
Parameter List

Table of Contents

Other manuals for YASKAWA iQpump1000

Related product manuals