H1 Multi-Function Digital Input Selections
H1-oo
Setting
Function LCD Display Description Page
82
<1>
PI Switch to Aux PI Switch to Aux
Closed: PI Auxiliary Control (Q6-oo) becomes the primary PI loop, disabling
the System PI controller (b5-oo). Overrides Q6-20 whenset to 0 (Disable Effect
on Speed Control).
83
Alternate Multi Setpoint
(Q1-02)
AltMultiSP Q1-02 Closed: Q1-02 becomes the PID setpoint
84
Alternate Multi Setpoint
(Q1-03)
AltMultiSP Q1-03 Closed: Q1-03 becomes the PID setpoint
85
Alternate Multi Setpoint
(Q1-04)
AltMultiSP Q1-04 Closed: Q1-04 becomes the PID setpoint
88
Volute-Thermostat
Normally Open
Volute-TStat NO
Function active when the drive is running.
Closed: Drive will trip on “VLTS - Volute-TStat Flt”
Open: Thermostat fault not active
Note:
Setting H1-oo = 88 and 89 simultaneously will trigger a “VLTS -
Volute-TStat Flt”.
89
Volute-Thermostat
Normally Closed
Volute-TStat NC
Function active when the drive is running.
Closed: Thermostat fault not active
Open: Drive will trip on “VLTS - Volute-TStat Flt”
Note:
Setting H1-oo = 88 and 89 simultaneously will trigger a “VLTS -
Volute-TStat Flt”.
8C Disable Pre-Charge Disable Pre-Chrg Closed: Pre-Charge disabled.
8D Multi Setpoint 1 Multi Setpoint 1
Open: Frequency reference, Q1-01, or Q1-03 is PID Setpoint.
Closed: Q1-02 or Q1-04 is PID Setpoint.
8E Multi Setpoint 2 Multi Setpoint 2
Open: Frequency reference, Q1-01, or Q1-02 is PID Setpoint.
Closed: Q1-03 or Q1-04 is PID Setpoint.
8F Low Water Level Low Water
Function active in AUTO Mode during normal operation, also used with Pre-
Charge function. Function logic depends on P1-30, Low Water Digital Input
Configuration.
P1-30 = 0 (Normally open)
Closed: Low water level fault
Open: Reservoir/Tank is filled to normal level
P1-30 = 1 (Normally closed)
Closed: Reservoir/Tank is filled to normal level
Open: Low water level fault
Pre-Charge function: Function uses the low water level input as “Tank/Reservoir”
feedback to indicate that the water level has been reached.
90 High Water Level High Water
Function active when the drive is running. Function logic depends on P1-31, High
Water Digital Input Configuration.
P1-31 = 0 (Normally open)
Closed: High water level fault
Open: Reservoir/Tank is filled to normal level
P1-31 = 1 (Normally closed)
Closed: Reservoir/Tank is filled to normal level
Open: High water level fault
92
Reset Accumulated
Volume
Reset Accum
Closed: Accumulated volume is reset to 0 and held at 0 if digital input remains
closed.
95 Remove Drive Disable Remote Drv Disbl
Closed: Prevents the drive from running when active for the time set in P4-26.
Must be inactive for the time set in P4-27 to allow the drive to run again.
Note: Parameter P4-25 determines if this input is normally open or
normally closed.
A8
Secondary PI Disable
(N.O.)
PI2 Disable N.O.
Closed: Disables the secondary PI controller. Output behavior depends on the
setting of S3-12.
A9
Secondary PI Disable
(N.C.)
PI2 Disable N.C.
Closed: Enables the secondary PI controller. Output behavior depends on the
setting of S3-12 when open.
AA
Secondary PI Inverse
Operation
PI2 Invert
Closed: Changes the sign of the secondary PI controller input (reverse acting PI
control).
AB
Secondary PI Integral
Reset
PI2 Intgrl Reset
Closed: Resets the secondary PI controller integral value.
AC
Secondary PI Integral
Hold
PI2 Intgrl Hold
Closed: Locks the value of the secondary PI controller integral value.
B.8 H Parameters: Multi-Function Terminals