Table 4.2 Manual Clock Adjustment Procedure by Setting o4-17 to 1
Procedure Display
1
The “Clock Not Set” display will appear if the Real-Time Clock data is not entered within 30
seconds of power-up of a drive with an HOA operator that has not yet been set.
- MODE -
DATA
DRV Rdy
ALM
FWD
ALM
Clock Not Set
Press F2 to Set
2
Use the up and down arrow keys to scroll through display menu until the screen shows
“Programming”.
- MODE -
HOME
PRG
ALM
Programming
FWD
3 Press the ENTER key to enter select the parameter setting mode.
- PRMSET - PRG
ALM
Initialization
A1-00 = 0
Select Language
FWD
ALM
HOME
DATA
4 Use the up and down arrow keys to scroll through display menu until parameter o4-17 appears.
- PRMSET - PRG
ALM
Maintenance
o4-17 = 0
Set time
FWD
ALM
HOME
DATA
5 Press the ENTER key until “0” flashes.
- PRMSET - PRG
ALM
Set time
o4-17= 0 *0*
- -
“0”
FWD
ALM
HOME
DATA
6 Press the up arrow key so that the display changes to “1”.
- PRMSET - PRG
ALM
Set time
o4-17= 1 *0*
Set
“0”
FWD
ALM
HOME
DATA
7
Press the ENTER key and the time setting screen will appear. Use the right arrow key to select
the desired digit, then set the correct date and time using the up and down arrow keys.
ALM
20 10/01/01 00:00
Second per month
+ 0 sec
YYYY/MM/DD HH:MM
ALM
8
After entering the correct time, press the ENTER key to save the changes.
The display will return to the display shown in step 5 and the alarm LED will be OFF.
n
o4-17: Real-Time Clock Setting (Resetting RTC to Factory Default)
No.
(Addr.
Hex)
Name Description Values
o4-17
(3100)
Set/Reset Real-time Clock
Sets the current date and time for the Real-Time Clock.
0: — — No Setting
1: Real-Time Clock Set
2: Real-Time Clock Reset
Default: 0
Range: 0 to 2