No. Parameter Name Setting Values
E2-01 Motor Rated Current
Default:
Min.: 10% of drive rated current
Max.: 200% of drive rated current
E2-04 Number of Motor Poles
Default: 2
Min.: 2
Max.: 48
L5-01 Number of Auto Restart Attempts
Default: 5
Min.: 0
Max.: 10
L5-04 Fault Reset Interval Time
Default: 20.0 s
Min.: 10.0
Max.: 3600.0
P1-06 Minimum Pump Speed
Default: 40.0 Hz
Min.: 0.0
Max.: [E1-04]
P5-02 HAND Reference
Default: 40.0 Hz
Min.: 0
Max.: [E1-04]
P5-04 HAND Key Function Selection
Default: 1
Range: 0, 1