When the “Disable Pre-Charge” digital input (H1-oo = 8C) is closed, even momentarily
• When the PID feedback satisfies Pre-Charge level (P4-01):
Feedback is greater than Pre-Charge Level (P4-01) (forward-acting PID, b5-09 = 0)
Feedback is less than Pre-Charge Level (P4-01) (reverse-acting PID, b5-09 = 1)
•
When the “Low Water” digital input (H1-oo = 8C) deactivates. A digital input must be programmed to “Low Water”
(H1-0o = 8F). The input is configured in P1-30 (0: normally open, 1: normally closed).
n
Related Parameters
No. Parameter Name Setting Values
P4-01 Pre-Charge Level
Default: 0.0 PSI
Minimum: 0.0
Maximum: 6000.0
P4-02 Pre-Charge Frequency
Default: 0.0 Hz
Minimum: 0.0
Maximum: [E1-04]
P4-03 Pre-Charge Time
Default: 0.0 min
Minimum: 0.0
Maximum: 3600.0
P4-05 Pre-Charge Loss of Prime Level
Default: 0.0 A
Minimum: 0.0
Maximum: 1000.0
P4-06 Pre-Charge Frequency 2
Default: 0.0 Hz
Minimum: 0.0
Maximum: [E1-04]
P4-07 Pre-Charge Time 2
Default: 0.0 min
Minimum: 0.0
Maximum: 3600.0
P4-08 Pre-Charge Loss of Prime Level 2
Default: 0.0 A
Minimum: 0.0
Maximum: 1000.0
H1 Multi-Function Digital Input Settings
H1-oo
Setting
Function Description
8C Disable Pre-Charge Closed: Pre-Charge disabled.
H2 Multi-Function Digital Output Settings
H2-oo
Setting
Function Description
A4 Pre-Charge Closed: Drive is in Pre-Charge mode.
R un
C omm an d
P re -C ha rg e
Sing le s peed – C o m plete via tim e r
“Pr e- cha rge
Active ”
M essage &
D igital Ou tpu t
(H 2-0x = A4)
Ou tpu t
F requen cy
P 4-0 3
Pre -cha rge T im e
P4-02 – Pre-cha rge F r equen cy
P4- 01 P re-cha rge level = 0.0 AND P 4-07 Pre-cha rge T im e 2 = 0.0 m in
PID N O T
disab le d
Figure 4.13 Pre-Charge Single Speed Complete via Timer
4.6 iQpump Presets and Functions
174
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual