n
Related Parameters, Monitors, and Multi-Function Digital Output Settings
No. Parameter Name Setting Values
P4-14 Two Motor Alternation Selection
Default: 0
Range: 0 to 3
P4-15 Two Motor Alternation Operation Selection
Default: 0
Range: 0, 1
P4-16 Two Motor Alternation Time
Default: 24.0 H
Range: 0.1 to 100.0 H
U1-82 Two Motor Time to Alternate Full scale: N/A
H2 Multi-Function Digital Output Settings
H2-oo
Function Description
43 2 Motor Alternate
Open: Motor 1 in use (or 2-motor alternation is disabled)
Closed: Motor 2 in use
4.6 iQpump Presets and Functions