HOA Keypad Display Fault Name
Drive fails to operate properly due to noise
interference
• Check the various options available to minimize the effects of noise.
• Counteract noise in the control circuit, main circuit, and ground wiring.
• Use only recommended cables or other shielded line. Ground the shield on the controller side or the drive
input power side.
• Ensure that other equipment such as switches or relays do not cause noise. Use surge suppressors if
required.
• Separate all communication wiring from drive power lines. Install an EMC noise filter to the drive power
supply input.
HOA Keypad Display Fault Name
CPF06
EEPROM Memory Data Error
Error in the data saved to EEPROM
Cause Possible Solution
There is an error in EEPROM control
circuit
• Turn off the power and check the connection between the control board and the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
The power supply was switched off while
parameters were being saved to the drive
Reinitialize the drive (A1-03 = 2220, 3330).
HOA Keypad Display Fault Name
CPF07 or CPF08 Terminal Board Connection Error
Cause Possible Solution
There is a faulty connection between the
terminal board and the control board
• Turn off the power and reconnect the terminal board.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
HOA Keypad Display Fault Name
CPF20 or CPF21 Control Circuit Error
Cause Possible Solution
Hardware is damaged
• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
HOA Keypad Display Fault Name
CPF22 Hybrid IC Failure
Cause Possible Solution
Hybrid IC failure on the power board
• Cycle power to the drive.
• If the problem continues, replace the power board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the power board.
HOA Keypad Display Fault Name
CPF23
Control Board Connection Error
Connection error between the control board and the drive
Cause Possible Solution
Hardware is damaged
• Turn off the power and check the connection between the control board and the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
HOA Keypad Display Fault Name
CPF24
Drive Unit Signal Fault
The drive capacity cannot be detected correctly (drive capacity is checked when the drive is powered up).
Cause Possible Solution
Hardware is damaged
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
HOA Keypad Display Fault Name
CPF25 Terminal Board Not Connected
Cause Possible Solution
5.2 Fault Detection