Step Display/Result
3.
Press to begin setting parameters.
- A.TUNE -
T1-01= 2 *2*
Term Resistance
PRG
Tuning Mode Sel
Rdy
ESC FWD DATA
4.
Press to display the value for T1-01.
- A.TUNE -
T1-01= 2 *2*
Term Resistance
PRG
Tuning Mode Sel
Rdy
FWD
“2”
5.
Save the setting by pressing .
Entry Accepted
6. The display automatically returns to the display shown in Step 3.
- A.TUNE -
T1-01= 2 *2*
Term Resistance
PRG
Tuning Mode Sel
Rdy
ESC FWD DATA
n
Enter Data from the Motor Nameplate
After selecting the type of Auto-Tuning, enter the data required from the motor nameplate.
Note: These instructions continue from Step 6 in “Selecting the Type of Auto-Tuning”.
Step Display/Result
1.
Press to access the motor output power parameter T1-02.
- A.TUNE -
T1-02= 0.75kW
(0.00 ~ 650.00)
PRG
Mtr Rated Power
Rdy
ESC FWD DATA
“0.75kW”
2.
Press to view the default setting.
- A.TUNE -
T1-02= 000.75kW
(0.00 ~ 650.00)
PRG
Mtr Rated Power
Rdy
FWD
“0.75kW”
3.
Press
F1
left
,
F2
right
, , , and to enter the motor power nameplate data in
kW.
- A.TUNE -
T1-02= 000.40kW
(0.00 ~ 650.00)
PRG
Mtr Rated Power
Rdy
FWD
“0.75kW”
4.
Press to save the setting.
Entry Accepted
5. The display automatically returns to the display in Step 1.
- A.TUNE -
T1-02= 0.40kW
(0.00 ~ 650.00)
PRG
Mtr Rated Power
Rdy
ESC FWD DATA
“0.75kW”
6.
Repeat Steps 1 through 5 to set the following parameters:
T1-03, Motor Rated Voltage (Rotational Auto-Tuning for V/f Control only)
T1-04, Motor Rated Current
T1-05, Motor Base Frequency
T1-06, Number of Motor Poles
T1-07, Motor Base Frequency (Rotational Auto-Tuning for V/f Control only)
T1-09, Motor No-Load Current (Stationary Auto-Tuning 2 only)
T1-10, Motor Rated Slip (Stationary Auto-Tuning 2 only)
- A.TUNE -
T1-
04
= X.XX A
(0.35 ~ 7.00)
PRG
Rated Current
ESC FWD DATA
“X.XX A”
- A.TUNE -
T1-03= 200.0VAC
(0.0 ~ 255.0)
PRG
Rated Voltage
ESC FWD DATA
“200.0VAC”
Note: To execute Stationary Auto-Tuning for line-to-line resistance only, set parameters T1-02 and T1-04.
5.8 Auto-Tuning
YASKAWA TOEP YAIP1W 01F YASKAWA AC Drive - iQpump1000 User Manual