n
Flange Type Heat Loss Data
Table 2.20 Models 4A0088 and 4A0103
Drive Model
Voltage
Class
Input Type
Heat Loss (W)
Wt. kg (lb)ND (Fc = 2 kHz) HD (Fc = 8 kHz)
Internal External Total Internal External Total
4A0088
400 6-Pulse
308 684 992 254 563 817 39 (85.8)
4A0103 357 848 1205 299 723 1022 39 (85.8)
n
Flange Type Panel Cutout Dimensions for External Heatsink Mounting
CUTOUT
Unit: in. [mm]
NOTES:
1. CUTOUT TOLERANCES:
+/- 0.02 in. [0.5 mm]
2. EXPOSED HEATSINK DEPTH
3. MINIMUM RECOMMENDED PANEL
THICKNESS: 12 GA
D=3.97 in. [101 mm] MINUS PANEL THICKNESS
(12)-1/4 in. [M6]
THREADED HOLES
Figure 2.32 Models 4A0088 and 4A0103
2.2 Flange Type Enclosure (NEMA 12 Backside) Dimensions & Heat Loss