5  Operation
5.2.6  Instantaneous Power Interruption Settings
5-16
5.2.6 Instantaneous Power Interruption Settings
Determines whether to continue operation or turn OFF the servomotor’s power when the power supply voltage 
to the main circuit power supply of the SERVOPACK and converter is interrupted.
If the power interruption time is shorter than the set value in Pn509, the servomotor will continue operation. If 
it is longer than the set value, the servomotor’s power will be turned OFF during the power interruption. The 
servomotor is turned ON when power supply to the main circuit recovers.
Note: If the instantaneous power interruption is longer than the set value of Pn509, the /S-RDY signal turns OFF.
If the uninterruptible power supplies are used for the control power supply and main circuit power supply, the 
SERVOPACK can withstand an instantaneous power interruption period of 50,000 ms max.
Pn509
Instantaneous Power Cut Hold Time
 
Classification
Setting Range Setting Unit Factory Setting When Enabled
20 to 50000  1 ms 20 Immediately Setup
•  If the control power supply makes control impossible during an instantaneous power 
interruption, the same operation will be performed as for normally turning OFF the 
power supply, and the setting of Pn509 will be ignored.
•  The holding time of the main circuit power supply varies with the output of the SER-
VOPACK. If the load on the servomotor is large and an undervoltage alarm (A.410) 
occurs, the setting of Pn509 will be ignored.
•  The holding time of the control power supply (24 VDC) depends on the capability of 
the power supply (not provided by Yaskawa). Check the power supply before using 
the application.
Position
Instantaneous power interruption
Set value for Pn509 ≥ OFF time (t)
Instantaneous power interruption
OFF time (t)
Power OFF
Set value for 
Pn509 ≥ OFF time (t)
Set value for 
      Pn509 < OFF time (t)
Main circuit
power supply
Set value for
Pn509
Servomotor
status
Power ON
Instantaneous power interruption
Set value for Pn509 < OFF time (t)
Instantaneous power interruption
Forced OFF
OFF time (t)
Main circuit
power supply
Set value for
Pn509
Servomotor
status
Power ON
Operation 
continues.