10.3 Main Commands and Subcommands
10.3.3 Command Details
10-20
Monitoring Parameters
( 7 ) User Constant RAM Writing
Description
Saves the parameter data written by executing Write User Constant in the Inverter volatile memory to validate the data.
With VSminiV7, the data written by executing Write User Constant will be validated without executing this command.
Setting Parameters
Monitoring Parameters
( 8 ) User Constant EEPROM Writing
Description
Saves the parameter data written by executing Write User Constant in the Inverter nonvolatile memory.
Setting Parameters
Name Register No.
Setting
Range
Remarks
Command Response Code
IW08 0 to 8 05: Alarm History Monitor
Command Status
IW09 Bit
Bit 0 (Command execution flag) ON during execution
Bit 3 (Command error completed
status)
ON when an error
occurs during com-
mand processing
Bit 8 (Command execution com-
pleted)
ON when command
execution is com-
pleted.
Status
IW10 Bit Inverter status
Response Alarm Code
IW30 0 to FFFFH Inverter alarm code
Inverter Alarm Code
IW32 0 to FFFFH The alarm history is read out
Name Register No. Setting Range Remarks
Command Code
OW08 0 to 8 06: User Constant RAM Writing
Name Register No.
Setting
Range
Remarks
Command Response Code
IW08 0 to 8 06: User Constant RAM Writing
Command Status
IW09 Bit
Bit 0 (Command execution flag) ON during execution
Bit 3 (Command error completed
status)
ON when an error
occurs during com-
mand processing
Bit 8 (Command execution com-
pleted)
ON when command
execution is com-
pleted.
Status
IW10 Bit Inverter status
Response Alarm Code
IW30 0 to FFFFH Inverter alarm code
Name Register No. Setting Range Remarks
Command Code
OW08 0 to 8 07: User Constant EEPROM Writing