Capacity Related Parameters B - 5
Capacity Related Parameter Values
Table B.4 480VAC Drives
Drive Model
CIMR-P7U
Nominal
Hp
Factory
Default
for
b8-04
Factory
Default
for
C6-02
and
C6-03
Factory
Default
for
E2-01
Factory
Default
for
E2-03
Factory
Default
for
E2-05
Factory
Default
for
L2-02
Factory
Default
for
L2-03
Factory
Default
for
L2-04
Factory
Default
for
L8-02
Factory
Default
for
L8-06
40P4 0.5/0.75 576.40 15kHz 1.0 0.6
38.198 0.1 0.1 0.3 95°C5
40P7 1
447.40 15kHz
1.6 0.8 22.459 0.1 0.2 0.3 95°C7.5
41P5 1.5/2
338.80 15kHz
3.1 1.4 10.100 0.2 0.3 0.3 95°C10
42P2 3
313.60 15kHz
4.2 1.5 6.495 0.3 0.4 0.3 90 °C10
43P7 5
245.80 15kHz
7.0 2.3 3.333 0.5 0.5 0.3 95°C12
45P5 7.5
189.50 15kHz
13.3 2.6 1.595 1.0 0.6 0.3 95°C10
47P5 10
145.38 15kHz
19.9 4.0 1.152 1.0 0.7 0.3 90°C20
4011 15/20
140.88 8kHz
26.5 5.6 0.922 2.0 0.8 0.3 95°C23
4015 25
126.26 10kHz
32.9 7.6 0.550 2.0 0.9 0.3 95°C17
4018 30 115.74 10kHz
52.3 7.8 0.403 2.0 1.0 0.6 98°C17
4030 40/50
92.54 8kHz
65.6 10.9 0.269 2.0 1.1 0.6 85°C20
4037 60
76.32 8kHz
79.7 19.1 0.155 2.0 1.1 0.6 85°C20
4045 75
71.56 8kHz
95.0 22.0 0.122 2.0 1.2 0.6 90°C20
4055 100
67.20 5kHz
130.0 24.0 0.088 2.0 1.2 1.0 90°C20
4075 125
46.20 5kHz
130.0 36.0 0.092 2.0 1.3 1.0 98°C16
4090 150
38.91 8kHz
156.0 40.0 0.056 2.0 1.5 1.0 108°C16
4110 200
36.23 5kHz
190.0 49.0 0.046 2.0 1.7 1.0 100°C16
4160 250
30.13 5kHz
270.0 70.0 0.029 2.0 1.8 1.0 108°C14
4185 300/350
30.57 2kHz
310.0 81.0 0.025 2.0 0.7 1.0 95°C15
4220 400/450
27.13 2kHz
370.0 96.0 0.020 2.0 0.8 1.0 100°C15
4300 500+
21.76 2kHz
500.0 130.0 0.014 2.1 0.9 1.0 95°C15
Note: b8-04 = Energy Savings Coefficiant
C6-02 = Carrier Frequency
C6-03 = Carrier Frequency Upper Limit
E2-01 = Motor Rated Current
E2-03 = Motor No-Load Current
E2-05 = Motor Line-to-Line Resistance
L2-02 = Momentary Power Loss Ride-Thru Time
L2-03 = Momentary Power Loss Minimun Base Block Time
L2-04 = Momentary Power Loss Voltage Recovery Ramp Time
L8-02 = Overheat Pre-Alarm Level
L8-06 = Input Phase Loss Detection Level