Programming 5 - 56
! o3 Digital Operator Copy Function
" o3-01 Copy Function Selection
Note: The copy function is disabled when serial communication is active.
" o3-02 Read Allowed Selection
The digital operator has parameter COPY capabilities via built in non-volatile memory. The digital operator can READ all of
the parameters in the Drive and store them for later WRITE back to the Drive or into a Drive with the same product code and
software number. In order to read the parameter values and store them in the digital operator, select o3-02= “1: Enabled”. If
you attempt to READ the data, which overwrites any previously stored data, without first setting o3-02= “1: Enabled”, you
will get the following error:
After setting o3-02= “1: Enabled”, it is possible to store parameter values in the digital operator by setting o3-01=1 (INV
OP
READ).
A successful READ of the parameter values will display:
An error may occur while saving the parameter values to the digital operator’s memory. If an error is displayed, press any key
to cancel the error display and return to parameter o3-01. Error displays and their meanings are covered in
Chapter 6: Diag-
nostics and Troubleshooting
of the E7 Users Manual (TM.E7.01). To COPY parameter values into a Drive, set o3-01= “2: OP-
>INV WRITE”. During the writing of the parameter values into the Drive the digital operator will display:
Setting Description
0 COPY SELECT (factory default)
1
INVOP READ
2
OPINV WRITE
3
OPINV VERIFY
Setting Description
0 Disabled (factory default)
1 Enabled
-
A
D
V
-
PRE
READ IMPOSSIBLE
-
A
DV-
READ
READ COMPLETE