Fault tracing 309
0310 USERSET LOAD
(0xFF69)
Loading of user set is not
successfully completed
because:
- requested user set does not
exist
- user set is not compatible
with drive program
- drive has been switched off
during loading.
Reload.
0311 USERSET SAVE
(0xFF69)
User set is not saved because
of memory corruption.
Check the setting of parameter 95.01 Ctrl
boardSupply.
If the fault still occurs, contact your local
ABB representative.
0312 UFF OVERSIZE
(0x6300)
UFF file is too big Contact your local ABB representative.
0313 UFF EOF
(0x6300)
UFF file structure failure Contact your local ABB representative.
0314 TECH LIB
INTERFACE
(0x6100)
Incompatible firmware
interface
Note: This fault cannot be
reset.
Contact your local ABB representative.
0315 RESTORE FILE
(0x630D)
Restoration of backed-up
parameters failed.
Contact your local ABB representative.
The fault is reset after a successful
restoration via the control panel or
DriveStudio.
0316 DAPS MISMATCH
(0x5484)
Mismatch between JCU
Control Unit firmware and
power unit logic versions.
Contact your local ABB representative.
0317 SOLUTION FAULT
(0x6200)
Fault generated by function
block SOLUTION_FAULT in
the application program.
Check the usage of the
SOLUTION_FAULT block in the
application program.
0318 MENU HIDING
(0x6200)
Menu hiding file missing or
corrupted.
Reload application.
Contact your local ABB representative.
Code Fault
(fieldbus code)
Cause What to do