EasyManua.ls Logo

ABB ACS850 - Alarms & Faults

ABB ACS850
370 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters 119
06.07 Torq lim status Torque controller limitation status word. -
06.12 Op mode ack Operation mode acknowledge: 0 = Stopped, 1 = Speed,
2 = Torque, 3 = Min, 4 = Max, 5 = Add, 10 = Scalar,
11 = Forced Magn (i.e. DC Hold)
1 = 1
06.13 Superv status Supervision status word. Bits 0…2 reflect the status of
supervisory functions 1…3 respectively. The functions are
configured in parameter group 33 Supervision (page 201).
-
06.14 Timed func stat Bits 0…3 show the on/off status of the four timers (1…4
respectively) configured in parameter group 36 Timed
functions (page 212). Bit 4 is on if any one of the four timers is
on.
-
06.15 Counter status Counter status word. Shows whether the maintenance
counters configured in parameter group 44 Maintenance
(page 224) have exceeded their limits.
-
08
08 Alarms & faults
Alarm and fault information.
08.01 Active fault Fault code of the latest fault. 1 = 1
08.02 Last fault Fault code of the 2nd latest fault. 1 = 1
No. Name/Value Description FbEq
Bit Name Information
0 Undervolt-
age
1 = Intermediate circuit DC undervoltage. *
1 Overvoltage 1 = Intermediate circuit DC overvoltage. *
2Minimum
torque
1 = Torque reference minimum limit is active. The limit is defined by
parameter 24.04 Minimum torq ref. *
3 Maximum
torque
1 = Torque reference maximum limit is active. The limit is defined by
parameter 24.03 Maximum torq ref. *
4 Internal cur-
rent
1 = An inverter current limit is active. The limit is identified by bits 8…11.
5 Load angle 1 = For permanent magnet motor and synchronous reluctance motor only:
Load angle limit is active, i.e. the motor cannot produce more torque.
6 Motor pull-
out
1 = For asynchronous motor only: Motor pull-out limit is active, i.e. the motor
cannot produce more torque.
7 Reserved
8 Thermal 1 = Input current is limited by main circuit thermal limit.
9 INU maxi-
mum
1 = Inverter maximum output current limit is active (limits the drive output
current I
MAX
). **
10 User cur-
rent
1 = Maximum inverter output current limit is active. The limit is defined by
parameter 20.05 Maximum current. **
11 Thermal
IGBT
1 = Calculated thermal current value limits the inverter output current. **
* One of bits 0…3 can be on simultaneously. The bit typically indicates the limit that is exceeded
first.
** Only one of bits 9…11 can be on simultaneously. The bit typically indicates the limit that is
exceeded first.
Bit Name Information
0 Ontime1 1 = On-time counter 1 has reached its preset limit.
1 Ontime2 1 = On-time counter 2 has reached its preset limit.
2 Edge1 1 = Rising edge counter 1 has reached its preset limit.
3 Edge2 1 = Rising edge counter 2 has reached its preset limit.
4 Value1 1 = Value counter 1 has reached its preset limit.
5 Value2 1 = Value counter 2 has reached its preset limit.

Table of Contents

Other manuals for ABB ACS850

Related product manuals