Control through the embedded fieldbus interface 315
The new settings will take effect when the drive is powered up the next time, or when
parameter 58.10 Refresh settings is activated.
58.35
…
58.58
Data I/O 1
…
Data I/O 24
0 (default) Defines the address of the drive parameter
which the Modbus master accesses when it
reads from or writes to the register address
corresponding to Modbus In/Out parameters.
Select the parameters that you want to read or
write through the Modbus I/O words.
Parameter Setting for
fieldbus control
Function/Information