Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
0.00 / real32Momentary cosphi of the drive.INU momentary cos
φ
1.25
100 = 1 / 100 = 1Cosphi.-1.00 ... 1.00
- / real32Rate of actual speed change. Positive values indicate
acceleration, negative values indicate deceleration.
See also parameters 31.32 Emergency ramp supervision,
31.33 Emergency ramp supervision delay, 31.37 Ramp
stop supervision and 31.38 Ramp stop supervision
delay.
Speed change rate1.29
1 = 1 rpm/s / 1 = 1
rpm/s
Rate of speed change.-15000...15000
rpm/s
0.000 Nm or lb·ft /
uint32
Torque that corresponds to 100% of nominal motor
torque. The unit is selected by parameter 96.16 Unit
selection.
Note: This value is copied from parameter 99.12 Motor
nominal torque if entered. Otherwise the value is
calculated from other motor data.
Nominal torque
scale
1.30
1 = 1 Nm or lb·ft /
1000 Nm or lb·ft
Nominal torque.0.000 ...
4000000.000 Nm or
lb·ft
- / real32Measured temperature of incoming cooling air. The
unit (°C or °F) is selected by parameter 96.16 Unit
selection.
Ambient
temperature
1.31
1 = 1 ° / 10 = 1 °Cooling air temperature.-40.0 ... 200.0 °
- / int16Amount of energy that has passed through the drive
(towards the supply) in full gigawatt-hours. The
minimum value is zero.
Inverter GWh
regenerating
1.32
1 = 1 GWh / 1 = 1 GWhRegenerative energy in GWh.0...32767 GWh
- / int16Amount of energy that has passed through the drive
(towards the supply) in full megawatt-hours. Whenever
the counter rolls over, 1.32 Inverter GWh regenerating
is incremented. The minimum value is zero.
Inverter MWh
regenerating
1.33
1 = 1 MWh / 1 = 1 MWhRegenerative energy in MWh.0...1000 MWh
- / real32Amount of energy that has passed through the drive
(towards the supply) in full kilowatt-hours. Whenever
the counter rolls over, 1.33 Inverter MWh regenerating
is incremented. The minimum value is zero.
Inverter kWh
regenerating
1.34
10 = 1 kWh / 1 = 1 kWhRegenerative energy in kWh.0...1000 kWh
0 GWh / int16Amount of net energy (motoring energy - regenerating
energy) that has passed through the drive in full
gigawatt hours.
You can reset the value by setting it to zero. Resetting
any of the parameters 1.35 to 1.37 resets all.
Mot - regen energy
GWh (resettable)
1.35
1 = 1 GWh / 1 = 1 GWhEnergy balance in GWh.-32768...32767 GWh
176 Parameters