Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
0 MWh / int16Amount of net energy (motoring energy - regenerating
energy) that has passed through the drive in full
megawatt hours. Whenever the counter rolls over, 1.35
Mot - regen energy GWh (resettable) is incremented or
decremented.
You can reset the value by setting it to zero. Resetting
any of the parameters 1.35 to 1.37 resets all.
Mot - regen energy
MWh (resettable)
1.36
1 = 1 MWh / 1 = 1 MWhEnergy balance in MWh.-1000...1000 MWh
0 kWh / real32Amount of energy (motoring energy - regenerating
energy) that has passed through the drive in full
kilowatt-hours.
Whenever the counter rolls over, 1.36 Mot - regen energy
MWh (resettable) is incremented or decremented.
You can reset the value by setting it to zero. Resetting
any of the parameters 1.35 to 1.37 resets all.
Mot - regen energy
kWh (resettable)
1.37
10 = 1 kWh / 1 = 1 kWhEnergy balance in kWh.-1000...1000 kWh
- / real32Absolute value of 1.1 Motor speed used.Abs motor speed
used
1.61
- / -Measured or estimated motor speed. For scaling, see
parameter 46.1.
0.00 ... 30000.00
rpm
- / real32Absolute value of 1.3 Motor speed %.Abs motor speed %1.62
10 = 1 % / 100 = 1 %Measured or estimated motor speed.0.00 ... 1000.00 %
- / real32Absolute value of 1.6 Output frequency.Abs output
frequency
1.63
- / -Estimated output frequency. For scaling, see parameter
46.2.
0.00 ... 600.00 Hz
- / real32Absolute value of 1.10 Motor torque.Abs motor torque1.64
- / -Motor torque. For scaling, see parameter 46.30.0 ... 1600.0 %
- / real32Absolute value of 1.14 Output power.Abs output power1.65
1 = 1 kW or hp / 100 =
1 kW or hp
Output power.0.00 ... 32767.00 kW
or hp
- / real32Absolute value of 1.15 Output power % of motor nom.Abs output power %
motor nom
1.66
10 = 1 % / 100 = 1 %Output power.0.00 ... 300.00 %
- / real32Absolute value of 1.17 Motor shaft power.Abs motor shaft
power
1.68
1 = 1 kW or hp / 100 =
1 kW or hp
Motor shaft power.0.00 ... 32767.00 kW
or hp
0.00 % / real32Measured temperature of incoming cooling air.
The amplitude range of 0…100 % corresponds to
0…60 °C or 32…140 °F.
See also 1.31 Ambient temperature.
Ambient
temperature %
1.70
1 = 1 % / 100 = 1 %Cooling air temperature.-200.00 ... 200.00 %