Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
1000 = 1 mA or V /
1000 = 1 mA or V
Forced value of analog input AI3.-22.000 ... 22.000 mA
or V
mA / uint16(Visible when 14.1 Module 1 type = FIO-11)
Shows the position of the hardware current/voltage
selector on the I/O extension module.
Note: The setting of the current/voltage selector must
match the unit selection made in parameter 14.60 AI3
unit selection. I/O module reboot either by cycling the
power or through parameter 96.8 Control board boot
is required to validate any changes in the hardware
settings.
AI3 HW switch
position
14.59
10Milliamperes.mA
2Volts.V
mA / uint16(Visible when 14.1 Module 1 type = FIO-11)
Selects the unit for readings and settings related to
analog input AI3.
Note: This setting must match the corresponding
hardware setting on the I/O extension module (see the
manual of the I/O extension module). The hardware
setting is shown by parameter 14.59 AI3 HW switch
position. I/O module reboot either by cycling the power
or through parameter 96.8 Control board boot is
required to validate any changes in the hardware
settings.
AI3 unit selection14.60
10Milliamperes.mA
2Volts.V
1 ms / uint16(Visible when 14.1 Module 1 type = FIO-11)
Selects a hardware filtering time for AI3.
See also parameter 14.62 AI3 filter time.
AI3 filter gain14.61
0No filtering.No filtering
1125 microseconds.125 us
2250 microseconds.250 us
3500 microseconds.500 us
41 millisecond.1 ms
52 milliseconds.2 ms
64 milliseconds.4 ms
77.9375 milliseconds.7.9375 ms
Parameters 255