Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
0.100 s / real32(Visible when 14.1 Module 1 type = FIO-11)
Defines the filter time constant for analog input AI3.
Unfiltered signal
Filtered signal
%
100
63
T
t
O = I × (1 - e
-t/T
)
I = filter input (step)
O = filter output
t
= time
T = filter time constant
Note: The signal is also filtered due to the signal
interface hardware. See parameter 14.61 AI3 filter gain.
AI3 filter time14.62
1000 = 1 s / 1000 = 1
s
Filter time constant.0.000 ... 30.000 s
0.000 mA or V /
real32
(Visible when 14.1 Module 1 type = FIO-11)
Defines the minimum value for analog input AI3.
See also parameter 14.21 AI tune.
AI3 min14.63
1000 = 1 mA or V /
1000 = 1 mA or V
Minimum value of AI3.-22.000 ... 22.000 mA
or V
10.000 mA or V /
real32
(Visible when 14.1 Module 1 type = FIO-11)
Defines the maximum value for analog input AI3.
See also parameter 14.21 AI tune.
AI3 max14.64
1000 = 1 mA or V /
1000 = 1 mA or V
Maximum value of AI3.-22.000 ... 22.000 mA
or V