Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
0.000 / real32(Visible when 14.1 Module 1 type = FIO-11)
Defines the real value that corresponds to the minimum
analog input AI3 value defined by parameter 14.63 AI3
min.
AI
scaled
(
14.57
)
AI
in
(
14.56
)
14.66
14.63
14.64
14.65
AI3 scaled at AI3 min14.65
1 = 1 / 1000 = 1Real value corresponding to minimum AI3 value.-32768.000 ...
32767.000
100.000 / real32(Visible when 14.1 Module 1 type = FIO-11)
Defines the real value that corresponds to the maximum
analog input AI3 value defined by parameter 14.64 AI3
max.
See the drawing at parameter 14.65 AI3 scaled at AI3
min.
AI3 scaled at AI3 max14.66
1 = 1 / 1000 = 1Real value corresponding to maximum AI3 value.-32768.000 ...
32767.000
- / uint16(Visible when 14.1 Module 1 type = FAIO-01)
The value of the analog output can be overridden for
eg. testing purposes. A forced value parameter (14.78
AO1 force data) is provided for the analog output, and
its value is applied whenever the corresponding bit in
this parameter is 1.
AO force selection14.71
1 = Force mode: Force AO1 to value of parameter 14.78
AO1 force data.
AO1b0
1 = Force mode: Force AO2 to value of parameter 14.88
AO2 force data (FAIO-01 only).
AO2b1
Reservedb2…15
1 = 10000h…FFFFh
Parameters 257