Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
14As selection 1 x Pt1000 analog I/O, but with two sensors
connected in series. Using multiple sensors improves
measurement accuracy significantly.
2 x Pt1000 analog
I/O
15As selection 1 x Pt1000 analog I/O, but with three
sensors connected in series. Using multiple sensors
improves measurement accuracy significantly.
3 x Pt1000 analog
I/O
16Pt1000 sensor connected to encoder interface 1. See
parameters 91.21 Module 1 temp sensor type and 91.22
Module 1 temp filter time.
Note: Pt1000 sensor is supported with FEN-11 and
FEN-31 encoder modules only.
Pt1000 encoder
module 1
17Pt1000 sensor connected to encoder interface 2. See
parameters 91.24 Module 2 temp sensor type and 91.25
Module 2 temp filter time.
Note: Pt1000 sensor is supported with FEN-11 and
FEN-31 encoder modules only.
Pt1000 encoder
module 2
130 ° / real32Defines the fault limit for temperature monitoring
function 2.
When measured temperature 2 exceeds the limit, the
drive trips on fault 4982 External temperature 2.
The unit is selected by parameter 96.16 Unit selection.
Note: With °F, the range is -76…1832. With a PTC sensor,
the range is 0…5000 ohms.
Temperature 2 fault
limit
35.22
1 = 1 ° / 1 = 1 °Fault limit for temperature monitoring function 2.-60...1000 °
110 ° / real32Defines the warning limit for temperature monitoring
function 2. When measured temperature 2 exceeds the
limit, a warning
(A492 External temperature 2) is generated.
The unit is selected by parameter 96.16 Unit selection.
Note: With °F, the range is -76…1832. With a PTC sensor,
the range is 0…5000 ohms.
Temperature 2
warning limit
35.23
1 = 1 ° / 1 = 1 °Warning limit for temperature monitoring function 2.-60...1000 °
Not selected / uint32Selects the input for parameter 35.21 Temperature 2
source, selections KTY84 analog I/O, 1 x Pt100 analog
I/O, 2 x Pt100 analog I/O, 3 x Pt100 analog I/O and
Direct temperature.
Temperature 2 AI
source
35.24
0None.Not selected
1Analog input AI1 on the control unit.AI1 actual value
2Analog input AI2 on the control unit.AI2 actual value
See Terms and abbreviations (page 169).Other [value]
0 °C / real32Defines the calibration of temperature 2.
See parameter 35.17 Temperature 1 calibration.
Temperature 2
calibration
35.27
1 = 1 °C / 1 = 1 °CCalibration of temperature 2 in celsius.-30...1000 °C
404 Parameters