Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
0Restart delay enable signal is disabled.Not selected
1Restart delay enable signal is enabled.Selected
2Digital input DI1 (10.2 DI delayed status, bit 0).DI1
3Digital input DI2 (10.2 DI delayed status, bit 1).DI2
4Digital input DI3 (10.2 DI delayed status, bit 2).DI3
5Digital input DI4 (10.2 DI delayed status, bit 3).DI4
6Digital input DI5 (10.2 DI delayed status, bit 4).DI5
7Digital input DI6 (10.2 DI delayed status, bit 5).DI6
10Digital input/output DIO1 (11.2 DIO delayed status, bit
0).
DIO1
11Digital input/output DIO2 (11.2 DIO delayed status, bit
1).
DIO2
12Parameter 74.1 ESP control word (page 519), bit 5 status
controls enable/disable status of the function.
ESP CW bit 5
See Terms and abbreviations (page 169).Other [bit]
2.0 s / real32Defines the time period for a drive to keep modulating
at speed defined with parameter 75.52 Kick start speed
reference.
Kick start hold time75.51
10 = 1 s / 10 = 1 sKick start hold time.0.0 ... 30.0 s
4.0% / real32Defines the speed reference used to perform kick-start
routine. The base value to calculate the kick start speed
reference is parameter 99.9 Motor nominal speed.
Kick start speed
reference
75.52
10 = 1% / 10 = 1%Kick start speed reference.0.5 ... 100.0%
100.0% / real32Defines the motor current reference used when the
kick-start routine is active. This current produces higher
starting torque necessary for the motor to overcome
static friction and starting spinning.
The base value to calculate the kick start current
reference is parameter 99.6 Motor nominal current.
Kick start current ref75.56
10 = 1% / 10 = 1%Kick start current ref.0.0 ... 300.0%
100.0 %/s / real32Defines the kick-start reference change rate facilitating
gradual increase of motor current.
Kick start current
ramp
75.57
10 = 1 %/s / 10 = 1
%/s
Kick start current ramp.0.0 ... 1000.0 %/s
ESP CW bit 6 / unit32Defines the source for the current pulse-start enable
signal.
For further information, see section
ESP production
mode
.
Note: This feature is applicable only for AC induction
motors.
Current pulse start
mode enable
75.60
0Restart delay enable signal is disabled.Not selected
1Restart delay enable signal is enabled.Selected
2Digital input DI1 (10.2 DI delayed status, bit 0).DI1
Parameters 529